Chapter 4—Troubleshooting
Troubleshooting Compact Field Panels
84
| 93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
Reinstalling the Mounting Tabs
Do the following to reinstall a DIN mounting tab:
1. Place the wire spring clip into the pocket in the channel for the mounting tab.
2. Make sure the mounting tab is face down.
3. Working from the center (inside) of the base, slide the mounting tab into the
channel. (See the following figure.)
NOTE:
The end with the screw hole slides into the channel first.
Figure 37: Reinstalling a DIN Mounting Tab.
Troubleshooting Compact Field Panels
Find the symptom below that best describes the problem and perform the corrective
action that follows.
If the problem persists or other symptoms are present, contact your Siemens Solution
Partner, Authorized TALON Dealer.
BATT LOW LED
The BATT LOW LED is on or the battery low warning is displayed at the
operator's terminal.
CAUTION
If you do not have a current backup, save the database before continuing.
1. Check that the mylar insert was removed from the AA (LR6) battery holder.
2. Check for polarity (+ to +) and (- to -).