Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes
0
75 |
93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
● Space between door panel and opening obstruction must be at least 11 inches
(279.4 mm) to allow for door removal at 40 degrees, or 28 inches (711 mm) with a
cabinet mounting at least 19 inches (483 mm) from the left side wall to allow door
to completely open at 135 degrees.
● 5 inches (127 mm) minimum horizontal distance between the enclosure and any
obstruction to the left and right.
● 7 inches (178 mm) minimum depth out from the wall on the left (hinged) side for
door clearance.