Operating Instructions

Table Of Contents
Chapter 2Hardware Features
HOA (Hand-Off-Auto) Upgrade Kits
0
35 |
93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
Users can override the default switch assignment or customize the switches to their
desired configuration.
The HOA module can be used to override outputs and monitor inputs.
The HOA mapping and definition of a logical point in the database can be done in
any order.
The HOA is hot-swappable. The module can be installed without powering down
the controller and interrupting facility operations.
The HOA module can also be remote mounted on the inside or outside of an
enclosure door, using an optional accessory sold separately.
HOA Specifications
Electrical
Power Consumption
Baud rate
5 V/60 mA
(from host controller)
38400
Dimensions
(L x W x D)
5.65 in. × 1.8 in. × 0.68 in.
(14.4 cm × 4.6 cm × 1.7 cm)
Weight
8 Switch
16 Switch
0.12 lb
0.14 lb
Operating Environment
Ambient Operating Temperature
Ambient Operating Temperature for rooftop (extended
temperature model)
Shipping and Storage
23°F to 122°F (-5°C to 50°C)
-40°F to 158°F (-40°C to 70°C)
-13°F to 167°F(-25°C to 70°C)
Agency Listings
UL Listing
cUL Listed
FCC Compliance
WEEE
RoHS
UL864 UUKL (except rooftop model)
UL864 UUKL7 (except rooftop model)
CAN/ULC-S527-M8 (except rooftop model)
UL 916 PAZX (all models)
Canadian Standards C22.2 No. 205-M1983, PAZX7
47 CFR Part 15