Chapter 2—Hardware Features
HOA (Hand-Off-Auto) Upgrade Kits
0
34
| 93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
TX-I/O Island Bus
The TC-36 offers the flexibility of expanding the total point count through a self-forming
island bus. With the addition of TX-I/O modules and a TX-I/O Power Supply, up to 16
points (or four TX-I/O modules) can be supported.
An additional license may be required to enable the Island Bus.
Compact Series Smoke Control Application
Requirements
CAUTION
The 115V or 230V PX Series Service Box is required for UL864 and NFPA92A
compliant installations. For more information, see the
PX Series Service Box
Assemblies Installation Instructions
(553-131) or the
Service Box Installation
Instructions
(586-135). For non-UL864 and non-NFPA92A applications, any 24 Vac
Class 2 transformer can be used.
NOTE:
For smoke control applications over BACnet/IP, the field panel must be connected to
the Automation Level Network (ALN) through an Ethernet switch that is UL Listed for
Fire Signaling. ALN and FLN circuits are supervised.
For smoke control applications, mount the TC Compact inside a 19-inch or 34-inch PX
Series enclosure (PXA-ENC19 or PXA-ENC34). For more information, see the
19" and
34" PX Series Enclosure Assemblies Installation Instructions
(553-130).
Service Modem Kit (538-915) is required for remote connection to the HMI of a TC
Compact running smoke control applications. The modem, serial cable, and surge
suppressor must be installed inside the 19-inch or 34-inch PX Series enclosure with a
Service Box.
For modems used with smoke control applications:
Modem Requirements
● The UL864 Listed surge protector (538-600) is required.
● Devices connected between the USB port and the UL Listed surge protector must
be located within the same room.
● A USB-to-RS-232 adaptor may be needed for UL Listed modems or UL Listed
printers that are not configured for USB communication.
● The modem may be located inside the PX Series enclosure.
HOA (Hand-Off-Auto) Upgrade Kits
HOA Upgrade Kits are available for TC Compact Series field panels. HOA Upgrade
Kits are not compatible with Unitary Equipment Controllers (UEC 16 or UEC 24). The
upgrade kits replace TC Compact covers with new covers equipped with manual
override switches and LEDs for visual feedback at the field panel.