Operating Instructions

Table Of Contents
Chapter 4Troubleshooting
Troubleshooting the TX-I/O Island Bus
73 |
79
Siemens Industry, Inc.
Owner's Manual
588-781
Building Technologies
2018-10-01
Troubleshooting the TX-I/O Island Bus
All points on the TX-I/O island bus are failed.
1. Verify all three signals, System Neutral ( ), Communication Data (CD), and
Communication Supply (CS) are connected throughout the entire TX-I/O island
bus.
The 24 Vac LED on the TX-I/O Power Supply is OFF.
1. Check for 24 Vac input.
2. Replace the fuse (4A, 5 × 20 mm, 250V, medium-acting, ceramic fuse).
The I/O module status LED (under the address key) is flashing or the I/O
point status LED is flashing on an open point. All points are operating
normally.
CAUTION
The TX-I/O™ island bus must extend from the male bus connector of the TX-I/O
Power Supply or Bus Connection Module.
The TX-I/O Power Supply and Bus Connection Module only supply 24 Vac to I/O
modules on the male bus connector.
I/O modules on the female bus connector of the TX-I/O Power Supply or Bus
Connection Module do not receive power and have a fault condition.
A point is failed or the point type displayed does not correspond to the
point type defined in the database.
1. Using the job drawing or TX-I/O Island Bus layout sheet, verify that the address
keys are in the correct module.
2. Reset the module to factory settings.
Verify that the module is supplied with 24 Vdc.
Remove keys that are in the wrong module.
Insert and then remove the reset key.
Cycle power to the module.
Insert the correct address key.
A current point on a Super Universal Module is failed.
Verify that the sensor supply wire is connected to the DC terminal (3, 11, 20, or
28).