Chapter 2—Hardware Features
Communication Connections
0
43 |
79
Siemens Industry, Inc.
Owner's Manual
588-781
Building Technologies
2018-10-01
Releasing Points
Do the following to change a point priority and release a point.
Figure 19: Point Action Release Priority Submenu
Menu/Submenu
Step
Description
Main Rotate
DIAL
to highlight
Points
.
Press
DIAL
/
OK
to select
Points
.
Displays the Points menu.
Points
Rotate
DIAL
to highlight
desired point.
Press
DIAL
/
OK
to select point. Displays the Point Action Release Priority submenu.
BACnet Point Action
Rotate
DIAL
to highlight
Release Priority
.
Press
DIAL
/
OK
to select
Release Priority
.
NOTE:
BACnet point priorities cannot be commanded lower
than a priority value of 8.
Rotate
DIAL
to change the
numeric value of the point
priority.
Press
DIAL
/
OK
to edit point
priority.
Rotate
DIAL
to change point
priority value.
Press
DIAL
/
OK
to confirm
change.
Releases BACnet point priority.
Press
ESC
.
Returns you to the previous menu without changing the
point priority.
P2 Point Action:
Rotate
DIAL
to highlight
Release Priority
.
Press
DIAL
/
OK
to select
Release Priority
.
Rotate DIAL to select Yes or
No. Press DIAL/OK.
This releases the priority to NONE.
Press
ESC
.
Returns you to the previous menu without changing the
point priority.
Figure 20: Release Priority Value Submenu