Product Description
The PXM10S and PXM10T modules are available as an upgrade for use with all
Siemens Compact and Modular Series field panels to provide additional local operator
capabilities. The PXM10S and PXM10T modules are field mounted and replace the
field panel covers.
There are three dedicated buttons, ALARM, INFO, ESC and one push DIAL. These
buttons, the push dial, and LCD display screen allow for interactive feedback at the
field panel controller.
The PXM10S and PXM10T modules support all the languages loaded in the host field
panel.
There are two versions of the modules as follows:
PXM10S has all available options, including Point Monitor and optional blue
backlight color.
PXM10T does not include the Point Monitor or the optional blue backlight color.
Language selection and user account timeout settings are configurable using an
operator workstation or HyperTerminal at the field panel’s HMI.
All PXM10S/T preferences are panel-specific and stored in the local panel
configuration data.
NOTE:
For more information on creating and configuring user accounts, see the TALON
Firmware User's Manual (588-580) (588-580).
Product Features
The PXM10S and PXM10T modules provide the following features:
Plug and Play - Upon connection to the host field panel, the device is recognized
and fully functional.
Hot Swappable The module can be installed or removed without powering down
the controller and interrupting facility operations.
User-friendly navigation and menu structure.
Push DIAL for easy operation.
Alarm button with red LED indicator for local alarm annunciations.
INFO button provides one touch access to detailed system information for points.
Manual and automatic login option for enhanced security or easy access.
View point information and status, view and acknowledge alarms, and
command/release local field panel points.
Point Monitor Can customize a group of points to continuously display and
refresh with updated values (PXM10S only).
Multi-language (English, Simplified Chinese, French, and Korean) support.
The PXM10S and PXM10T modules can also be mounted on the inside or outside
of an enclosure door, using an optional accessory sold separately.
Communication Connections
A field panel fully powered and running Firmware Revision 3.2.2 or later, recognizes
the PXM10S and PXM10T modules within approximately 5 seconds of connection.
Prior to that, the Operator Display is not operational.