Operating Instructions

Table Of Contents
Chapter 2Hardware Features
Communication Connections
0
27 |
79
Siemens Industry, Inc.
Owner's Manual
588-781
Building Technologies
2018-10-01
FLN devices on the Expansion Module
Electrical Rating
Power Requirements 24 Vac +/-20% input @ 50/60 Hz
Power Consumption (Maximum) 24 VA @ 24 Vac
AC Power NEC Class 2
Communication NEC Class 2
Operating Environment
Ambient operating environment
Operate in a dry location, which is protected from exposure to salt spray or other corrosive
elements. Exposure to flammable or explosive vapors must be prevented.
Shipping and storage environment -13°F to 158°F (-25°C to 70°C)
Relative Humidity 5% to 95% rh, non-condensing
Mounting Surface
Building wall or structural member (Do not mount on HVAC components or any other vibrating
surface.)
CE Compliance
Requires installation inside a metal enclosure rated at IP30 minimum.
Smoke Control Applications
Requires installation inside a PX series enclosure
Vibration Compliance to IEC 60721, 3M2, and 2M2
Protection to EN60529 IP 20
Agency Listings
UL
UL 864 UUKL Smoke Control Equipment
UL 864 UUKL7 Smoke Control Equipment
CAN/ULC-S527-M8
UL 916 PAZX
UL 916 PAZX7
Agency Compliance
CFR47 Part 15, Class A; CFR47 Part 15, Class B - with metal enclosure, maximum opening
Australian EMC Framework - with metal enclosure, maximum opening size is 34"
European EMC Directive (CE) - with metal enclosure, maximum opening size is 34"
RoHS Compliant
OSHPD Seismic Certification
Product meets OSHPD Special Seismic Preapproval certification (OSH-0218-10) under California
Building Code 2010 (CBC2010) and International Building Code 2009 (IBC2009) when installed
within the following Siemens enclosure part numbers: PXA-ENC18, PXA-ENC19, or PXA-ENC34.
Electrical Disturbance Testing
Dips and Interrupts per EN 61000-4-11
Electrical Fast Transients (EPT) per EN 61000-4-4, 1 kV signal, 2 kV AC power
Electrical Surge Immunity
per EN 61000-4-5
AC power: 2 kV common mode, 1 kV differential mode
Signal lines: 1 kV CM, 5 kV DM
Electrostatic Discharge (ESD) per EN 61000-4-2, 4 kV contact, 8 kV air discharge
RF Conducted Immunity per EN 61000-4-6 @ 10V
RF Radiated Immunity per EN 61000-4-3 @ 10V/m