Operating Instructions

Troubleshooting
Siemens Building Technologies, Inc. 7-7
This exception indicates that an internal error occurred while processing a System 600
APOGEE block. The block may be corrupted and should be deleted from the FIX database
and recreated.
NETWORK EXCEPTION - FindPoint
This exception indicates that a System 600 APOGEE network could not be located or the
corresponding object in the Proxy Database could not be created while attempting to find a
System 600 APOGEE point on the network. The network specification may be incorrect.
Point addresses have the following format:
network.trunk.cabinet.point
where the network is the name defined in the Registry entry:
HKEY_LOCAL_MACHINE\Landis&Staefa\Intellution\PlugIn\ ProxyNetwork
POINT EXCEPTION - FindPoint
This exception indicates that a System 600 APOGEE network could not be located or the
corresponding object in the Proxy Database could not be created while attempting to find a
System 600 APOGEE point on the network. The point specification may be incorrect. Point
addresses have the following format:
network.trunk.cabinet.point
where the point is a valid System 600 APOGEE point name.
POINT TYPE EXCEPTION - FindPoint
This exception indicates that the point type of a System 600 APOGEE block does not match
the point type of the corresponding point found on the network. Delete the block from the FIX
database or the point from the System 600 APOGEE cabinet and recreate the block or point
with the correct point type.
TAG ERROR - FindPoint, GetAttributes, Register, SetAttributes,
Unregister
This exception indicates that an internal error occurred while processing a System 600
APOGEE block. The block may be corrupted and should be deleted from the FIX database
and recreated, if it can be identified from the message.
TRUNK EXCEPTION - FindPoint
This exception indicates that a System 600 APOGEE trunk could not be located or the
corresponding object in the Proxy Database could not be created while attempting to find a
System 600 APOGEE point on the network. The trunk specification may be incorrect. Point
addresses have the following format:
network.trunk.cabinet.point
where the trunk is a string of the form: P2Trunk_0.