Operating Instructions

System 600 APOGEE Database Dynamos for Intellution's 32-Bit FIX Owner's Manual
7-6 Siemens Building Technologies, Inc.
This exception indicates that an internal error occurred while processing the point address
from a System 600 APOGEE block. The block may be corrupted and should be deleted from
the FIX database and recreated.
ADDRESS EXCEPTION - FindPoint
This exception indicates that an incomplete or badly formed System 600 APOGEE point
address was found in the named System 600 APOGEE block when attempting to locate a
System 600 APOGEE point on the network. Point addresses have the following format:
network.trunk.cabinet.point
ATTRIBUTE ERROR - GetAttributes, SetAttributes
This exception indicates that an internal error occurred while processing a request to read
from or write to a System 600 APOGEE point. The corresponding block may be corrupted
and should be deleted from the FIX database and recreated.
ATTRIBUTE EXCEPTION - FindPoint, GetAttributes, Refresh, Register,
SetAttributes, Unregister
This exception indicates that an attempt to read from or write to a System 600 APOGEE point
failed. This failure is generally the result of competition by applications accessing the Proxy
Database, and is normal under high load conditions such as system startup or System 600
APOGEE network failures. The operation may be repeated automatically depending on the
application that generated the failure.
BIND EXCEPTION - GetAttributes, Refresh, Register, SetAttributes,
Unregister
This exception indicates that an attempt to “bind” or gain access to a Proxy Database object
failed during a System 600 APOGEE block operation. This failure can occur due to
competition by applications accessing the Proxy Database. However, if this failure occurs
repeatedly for the same System 600 APOGEE block, the corresponding object in the Proxy
Database may be corrupted and must be purged by restarting FIX and the MSG service.
CABINET EXCEPTION - FindPoint
This exception indicates that a System 600 APOGEE cabinet could not be located or the
corresponding object in the Proxy Database could not be created while attempting to find a
System 600 APOGEE point on the network. The cabinet specification may be incorrect. Point
addresses have the following format:
network.trunk.cabinet.point
where the cabinet field panel is a number from 0 - 99.
HANDLE ERROR - FindPoint, GetAttributes, Refresh, Register,
SetAttributes, Unregister