• Result (RESULT)
This status indicates whether the last command sent by the operator was successful.
This is most useful for the “Get Totalized Value” command. If the Totalized value does
not change after sending the command, the result status will indicate whether the
command was successful, indicating that the totalized value has not changed or if there
was an error in processing the command.
Data Link Design Considerations
Table 6-3 and Table 6-5 provide detailed information about each field, which is important for
screen design considerations.
Table 6-1. Point Attribute Field Design.
Point Name Description Read/
Write
Point Types
Used With
Information
A_ADDRESS Network Address R/W* ALL 128 Character Dotted Address
A_ALARM_LVL Enhanced Alarm Level R ALL “Non-Enhanced”, “Level n”, n=1
to 6
F_ALARM_LVL 0, 1 to 6
A_COV_LIMIT COV Limit R LAI, LAO,
LPACI
13 Characters
F_COV_LIMIT Working Range
A_CV Current (Present) Value R/W All 13 Characters
F_CV Working Range
A_DESCRIPTOR Point Descriptor R All 17 Characters
A_ETAG Engineering Units R LAI, LAO,
LPACI
7 Characters
A_HI_ALARM Hi Alarm Limit R LAI, LAO,
LPACI
13 Characters
F_HI_ALARM Working Range
A_IV Initial Value R/W Except LAI,
LDI
13 Characters
F_IV Working Range
A_LO_ALARM Low Alarm Limit R LAI, LAO 13 Characters
F_LO_ALARM Working Range
A_PRIORITY Command Priority R/W All “None”, “PDL”, “Emergency”,
“Smoke”, “Operator”
F_PRIORITY 0, 5, 32, 34, 35
A_TOTAL Totalized Value R Except LPACI 13 Characters
F_TOTAL Working Range
* Writable from Database Builder only