Operating Instructions

System 600 APOGEE Blocks
Siemens Building Technologies, Inc. 4-15
Logical Fast/Slow/Stop Pulsed (LFSSP)
Figure 4-13 shows the dialog box used to configure an LFSSP point block. An LFSSP
provides three commandable pulsed digital outputs (FAST/SLOW/STOP) and one optional
digital input used as a proof.
Figure 4-13. Logical Fast/Slow/Stop Pulsed Dialog Box.
Most of the fields in Figure 4-13 are the same as those described for the LAI block. Refer to
the LAI descriptions for more information regarding these fields. The two exceptions are the
addition of the Initial Value field, and the replacement of the Engineering Limits field with the
Labels field.
Initial Value
For Intellution programming use. Allows the operator to set the value of a point when it is
placed on scan (e.g., to turn on all fans before a batch is run). This does not affect the initial
value set in field panels.
Labels
Can be a label of up to 13 characters. System 600 APOGEE labels are the default and may
be overridden by entering the label of choice. Defaults are listed in Table 4-12.
Table 4-12. Default Labels.
Floating Point ASCII
0.0 STOP
1.0 SLOW
2.0 FAST