Table 4-4. Minimum and Maximum Value Fields.
Field
Panel
Point Module Type Point
Type
Sensor Type Min. Point Value Max. Point Value
MBC Al_E (0–10 Vdc) LAI V (Voltage)
=m( 3,584 ) + b =m(29,184) + b
MBC Al_I (4-20 mA) LAI I (Current)
=m( 3,584 ) + b = m(29,184) + b
MBC Al_100K ohms LAI T (Thermistor)
=-40°F(-17.7°C ) =257°F(125°C)
MBC Al_RTD LAI I (Current)
=m(11543) + b =m(18571)+b
MBC AO_E (0–10 Vdc) LAO N/A
=
b
=
m
(30,720)+
b
MBC AO_I (4–20 mA) LAO N/A
=b = m(30,720)+b
MBC AO_P (0–20 psi) LAO N/A
=
b
=
m
(30,720)+
b
ALL Virtual LAI/LAO N/A
=b = m(32,767)+b
SCU Al_E (0–10 Vdc) LAI V (Voltage)
=b =4000m+b
SCU Al_I (4–20ma) LAI I (Current)
=b+800m =4000m+b
SCU Al_P LAI T (Thermistor)
=b+1120m =2400m+b
SCU AI_100K LAI T (Thermistor)
=-40°F(-17.7°C ) =257°F(125°C)
SCU AO_E LAO N/A
=b =m(255) + b
SCU AO_I LAO N/A
=b =m(255) + b
SCU AO_P LAO N/A
=b =m(255) + b
RCU P2 Al_E (0–10 Vdc) LAI V (Voltage)
=b + 4200 =m(21000) + b
RCU P2 AO_E LAO N/A
=
b
=
m
(1023) +
b
RCU P2 AO_P LAO N/A
=
b
+ 42 =
m
(255) +
b
where:
m = slope value for the point
b = intercept value for the point