Operating Instructions

System 600 APOGEE Database Dynamos for Intellution's 32-Bit FIX Owner's Manual
4-6 Siemens Building Technologies, Inc.
Example:
PC_1.P2Trunk_0.12.OATEMP
NT workstation is PC_1
Point OATEMP is located in cabinet 12 on trunk 0
NOTE:
When creating multiple blocks, cut and paste the network address from one
block to the next to avoid retyping the common portions of the field.
Descriptor
System 600 APOGEE point description as defined in the System 600 APOGEE panel.
Priority
Reflects either a point's current priority (if reading the point attribute) or desired priority (if
writing the point attribute). Table 4-3 lists the priorities in ascending order, with None being
the lowest priority and Operator being the highest.
Table 4-3. Point Priorities.
Floating Point Siemens Building Technologies, Inc. Text Meaning
0 None
5PDL
32 Emergency
34 Smoke
35 Operator
Character
This field displays an overview of the point's characteristics in the following format:
A EA PA TE TH BOI BINC CBE
Where:
A identifies if the point is defined as Alarmable
EA identifies if the point is defined for Enhanced Alarming
PA identifies if the point is defined for Printing of Alarms
TE identifies if Totalization for the point is Enabled
TH identifies if Totalization is in Hours
BOI identifies if the point is defined to have its Binary Output Inverted
BINC identifies if the point is defined to have its Binary Input Normally Closed
CBE identifies if the point is defined to have Both Edges counted for totalization
(applies to LPACI point type only)
NOTE:
When the above conditions are true, the abbreviations are displayed. When
the condition is false, the field is empty.