Operating Instructions

System 600 APOGEE Blocks
Siemens Building Technologies, Inc. 4-5
The System 600 APOGEE blocks have a default of 10 seconds for Scan Time which is
appropriate for these blocks when used as stand-alone blocks. If the System 600 APOGEE
blocks are used as primary blocks in a chain, the chain will use the Scan Time for the
processing rate.
There are two types of scan time:
Table 4-2 shows Time Based scans:
Table 4-2. Time-Based Scan Times.
Increment Range
Subseconds 0.05 –- 0.95
Seconds 1 — 59
Minutes 1M –- 59M
Hours 1H –- 24H
One-shot processing:
SAC program processes a block only once. The block does not trigger again unless the
SAC is restarted, and the database is reloaded. To process a block only once, enter zero
(0) in the Scan Time field.
I/O Device
System 600 APOGEE virtual I/O device. No other choice is supported.
Address
Station – Windows NT workstation name given to the Intellution node containing the
FIX database for this block. The name can be verified by pointing to the Start button,
and clicking Settings, Control Panel, Network, Identification, and Computer
Name.
Network Trunk – Name or number of the System 600 APOGEE P2 network trunk on
which the point is located. This field is case sensitive. Refer to the example on the
following page.
Cabinet Number – Number of the System 600 APOGEE field panel where the point
resides.
Point Name – System 600 APOGEE Point Name.