Operating Instructions

System 600 APOGEE Database Dynamos for Intellution's 32-Bit FIX Owner's Manual
4-4 Siemens Building Technologies, Inc.
Description
Alphanumeric explanation of Tag Name displayed in Alarm Summary, Reports, View. You
can use a maximum of 40 alphanumeric characters.
NOTE:
This is the FIX description, not the System 600 APOGEE point descriptor
resident in the System 600 APOGEE field panel.
Start Block on Scan
Scan, Alarm, and Control (SAC) automatically processes all primary blocks that have this box
checked whenever SAC starts or the database is loaded.
Initial Mode
Automatic - sends/receives data to/from System 600 APOGEE devices.
Manual - accepts data from the keyboard, another block, or a command script.
NOTE:
This is similar to the System 600 APOGEE concept of points being online or
offline, with online correlating to automatic.
NOTE:
Most primary blocks are set as automatic and secondary blocks as manual.
Scan Time
The interval that determines how often the Scan, Alarm, and Control (SAC) program
processes a block in the process database (PDB).
NOTE:
System 600 APOGEE Blocks do not depend on the SAC Scan Time for
reading and writing block values. This is similar to the function of a FIX PLC
register block.