Operating Instructions
System 600 APOGEE Database Dynamos for Intellution's 32-Bit FIX Owner's Manual
4-2 Siemens Building Technologies, Inc.
Run the Intellution Database Dynamo Configurator utility BTKCFG.EXE to add or remove
supported Database Dynamo Block types. Export any existing FIX32 databases before
running this utility.
NOTE:
The Logical Controller (LCTLR) point type is not supported by the Database
Dynamos.
Point Type Definitions
The following System 600 APOGEE point types are supported by FIX:
• Logical Analog Input (LAI) - Monitors the value of an analog input point (e.g.,
temperature, flow, pressure).
• Logical Analog Output (LAO) - Provides one commandable analog output point
(e.g., position valves and dampers).
• Logical Digital Input (LDI) - Monitors the state of digital input points (e.g., fans and
lighting).
• Logical Digital Output (LDO) - Provides one commandable digital state (used to
command two-position ON/OFF devices such as fans and lighting).
• Logical Two-State Latched (L2SL) - Provides one commandable latched digital
output (ON/OFF) and monitors one digital input for proof.
• Logical Two-State Pulsed (L2SP) - Provides two commandable pulsed digital
outputs (ON/OFF) and monitors one latched digital input as a proof point.
• Logical FAST/SLOW/STOP Latched (LFSSL) - Provides commandable latched
digital outputs (FAST/SLOW/STOP) and one optional digital input as a proof.
• Logical FAST/SLOW/STOP Pulsed (LFSSP) - Provides three commandable pulsed
digital outputs (FAST/SLOW/STOP) and one optional digital input used as a proof.
• Logical ON/OFF/AUTO Latched (LOOAL) - Provides two commandable latched
digital outputs and one digital input that can be used as a proof point.
• Logical ON/OFF/AUTO Pulsed (LOOAP) - Provides two commandable latched
digital outputs (ON/OFF) and one commandable latched output (AUTO). The digital
input may be used as an optional proof point.
• Logical Pulsed Accumulator (LPACI) - Counts pulses of one digital input point.