Operating Instructions

Siemens Building Technologies, Inc. 4-1
4
System 600 APOGEE Blocks
Chapter 4 explains adding System 600 APOGEE points in a FIX database.
This chapter discusses the following topics:
Overview
Point Type Definitions
Overview
There are two ways to enter System 600 APOGEE points in a FIX Database.
Use the System 600 APOGEE - Intellution 32-Bit FIX Conversion Utility described in
Chapter 5. This conversion utility is useful for automating the entry of a large number
of points.
Use the System 600 APOGEE block dialog boxes, similar to the generic block dialog
boxes used while editing a FIX database. There are eleven System 600 APOGEE
block dialog boxes used to configure database blocks for eleven of the System 600
APOGEE point types. Table 4-1 lists the eleven System 600 APOGEE points that
can be directly configured on a FIX node.
Table 4-1. System 600 APOGEE Points Supported by FIX.
Point Type Description Database Dynamo
LAI Logical Analog Input btk_lai.dll
LAO Logical Analog Output btk_lao.dll
LDI Logical Digital Input btk_ldi.dll
LDO Logical Digital Output btk_ldo.dll
L2SL Logical Two State Latched btk_l2l.dll
L2SP Logical Two State Pulsed btk_l2p.dll
LFSSL Logical Fast/Slow/Stop Latched btk_lfl.dll
LFSSP Logical Fast/Slow/Stop Pulsed btk_lfp.dll
LOOAL Logical On/Off/Auto latched btk_lol.dll
LOOAP Logical On/Off/Auto Pulsed btk_lop.dll
LPACI Logical Pulsed Accumulator Input btk_lpa.dll