Room usage scenarios
In offices the following scenarios are assumed to be most likely:
HVAC
This could be a possible HVAC scenario:
The room temperature is increased at 6.00 - controlled by a time schedule – to the
Precomfort temperature setpoint (20 °C) and reduced again at 21.00 to the Economy tem-
perature level (18 °C). Also, when people enter the room, the temperature is increased to the
Comfort level (21 °C) and reduced again when people leave.
Lights
This could be a possible light scenario:
When people enter the room the light goes on automatically. Manually switching on the lights
via the push buttons could also possible. After a certain time after they have left the room, all
lights are automatically turned off. The lighting groups are dimmed according to the natural
light contribution to maintain a constant brightness level in the room when occupied.
Blinds
This could be a possible blind scenario:
Blinds are controlled automatically. However, a manual intervention is still possible at any
time. After sunrise, the blinds are automatically raised. When the sun shines on the facade,
the blinds are driven to a certain position to protect people from excessive solar irradiance by
maintaining comfortable lighting conditions in the room. After sunset or after people have left
the room, the blinds are automatically lowered.