Application Guide
High-end application
No. 07
Conference Room – Room Automation
Synco
™
& Gamma
39
V
AV + floor heating with light, blinds
control
acc
ording
to occupancy
for large office or conference rooms
Highlights
· Fully integrated VAV application with temperature, CO
2
and air volume control
· Automatic data exchange between room HVAC and the primary plant
· VAV controllers to optimize the air system
· Remote control of individual rooms or room groups
Room setup
· RDU341 or RDG400KN, Room thermostat: The room thermostat measures the room temperature and
calculates the heating / cooling demand which is sent to the heating / cooling controller and to the VAV
controller. It also controls the valve actuator STA23 of the floor heating.
· GDB181.1E/KN, VAV controller: The GDB… controls the VAV dampers. It’s air volume setpoints are
shifted according to the air demand from the room thermostat.
· AQR2576, air quality sensor: The AQR2576 sends the air quality data to the air handling controller
which controls the fresh air quantity of the supply air. The AQR offers two digital inputs to connect a
standard wall switch to operate lights and blinds.
· UP 258E21, presence detector: The UP 258 detects occupancy in the room and measures the
brightness. These data are distributed to the room thermostat and the KNX/DALI gateway.
· N 141/02, KNX/DALI Gateway: The N 141 transfers the KNX signal to the DALI bus to switch and dim
the lights. In the other direction it sends status information such as the failure or operating hours of a lamp
to the KNX bus.
· N 523/04, blind actuator: The N 523 is controlled by the weather station and drives the blinds and its
slats to the required position.
· AP 257/22, weather station: The AP 257 measures the outside temperature, brightness and windspeed
and calculates drive commands for the blind actuator.