User Manual

Advanced application
No. 06
Meeting Room – Room Automation
Synco
& Gamma
Ventilation with
radiator
heating
with blinds, light
control
according to
occupancy
Highlights
· Flush mount sensor for CO
2
control
· Room box, the modular system for room automation
· Remote control of individual rooms or room groups
Room setup
· UP 237K, Room temperature controller: The UP 237K measures the room temperature and controls
the radiator heating via the thermo drive actuator. It allows to operate the heating and the fan.
· AQR2576, Flush mount sensor: The AQR2576 measures the air quality (CO
2
) and controls the fan
accordingly in the auto mode. The AQR offers two digital inputs to connect a standard wall switch to
operate lights and blinds.
· UP 258E21, presence detector: The UP 258 detects occupancy in the room and measures the
brightness. These data are distributed to the AQR2576, to the UP 237 and the devices in the room box.
· AP 641, room box: The room box includes the universal dimmer RS 525/23, the shutter actuator RL
521/23 and the binary output RS 510/23 to control the lights, blinds and the fan.
· N 605, thermo drive actuator: The N 605 receives the heat command from the Contouch room
temperature controller and drives the valve actuator STA23 of the floor heating.
· AP 257/22, weather station: The AP 257 measures the outside temperature, brightness and windspeed
and calculates drive commands for the blind actuator.
· RMB795B, central control unit: The RMB795B is the room group manager which provides individual
time schedules for up to 10 rooms or room groups.