User Manual

Advanced application
No. 04
Meeting Room – Room Automation
Synco
& Gamma
25
Device list
Key Product no. and description Stock no.
1 UP 204 Contouch room controller 5WG1 204-2AB11
2 UP 258E21 presence detector 5WG1 258-2EB21
3 AP 641 room box 5WG1 641-3AB01
4 RS 525/23 universal dimmer 5WG1 525-2AB23
5 RL 521/23 shutter actuator 5WG1 521-4AB23
6 RS 510/23 binary output 5WG1 510-2AB23
7 N 605 thermo drive actuator 5WG1 605-1AB01
8 STA23 electro thermal actuator S55174-A101
9 RMB795B central control unit S55370-C162…C167
10 AP 257/22 weather station 5WG1 257-3AB22
11 RMH760B heating controller RMH760B-x
12 OZW772.x Web server OZW772.x
13 N 125/12 power supply 5WG1 125-1AB12
Variant
Key Product no. and description Stock no.
12a N 152 IP control center 5WG1 152-1AB01
Control of room
HVAC
Floor or radiator heating and ventilation with heat exchanger
· Heating control
· Manual control of a single or 2-stage fan for fresh air
supply
· On/off, PWM or PI-control or sequence control of heat-
ing actuator
Control of heating
HB0001 H6B HQ
Demand-compensated boiler temperature control with con-
trolled maintained boiler return temperature
· Demand-compensated boiler temperature control
· Controlled maintained boiler return temperature with
mixing valve
· Control of a boiler pump according to boiler operating
mode
· Control of a single-stage or 2-stage burner
· Control of the boiler temperature via modulating burner
with DC 0…10 V control
The temperature of each office or meeting room is acquired and individually controlled. The fan can be operated on
the Contouch room controller or controlled by the presence detector. The heating plant is controlled in dependence
on the outside temperature and the heat demand from the rooms. Non-occupancy periods during the night can be
programmed in a time scheduler for each room. During these time periods (night, weekend, holidays), the room
temperatures are automatically reduced. Also during the day the temperature is slightly reduced when the room is
not occupied.