Parameter Setting Function Remarks
5. Parameter settings on room thermostat 1, RDG400KN
Settings for the zones
Path: ... > Communication
P82 - geographical
zone (apartm)
4 Room group number
P83 - geographical
zone (room)
2 Room number Consecutive numbering 1-x when
there are several RDG in the same
room group
P87 - air distribu-
tion zone
1 Air distribution zone
6. Parameter settings on on VAV controller supply air, GDB181.1E/KN
Parameter settings
Path: ... > Operation settings
Master / Slave Master Supply air VAV controller
Minimum volume
flow
25%
Maximum volume
flow
95%
Settings for the zones
Path: ... > Communication
Geographical zone
(apartm)
4 Room group number
Geographical zone
(room)
1 Room number
Air distribution
zone
1 Air distribution zone
7. Parameter settings on VAV controller extract air, GDB181.1E/KN
Parameter settings
Path: ... > Operation settings
Master / Slave Slave Extract air VAV controller
Minimum volume
flow
0%
Maximum volume
flow
100%
Settings for the zones
Path: ... > Communication
Geographical zone
(apartm)
4 Room group number
Geographical zone
(room)
1 Room number
Air distribution
zone
1 Air distribution zone