Synco 200 – Commissioning guide Answers for infrastructure.
Synco 200 – Commissioning guide This guide provides basic instructions for configuring and starting the Synco™ 200 controllers. It contains tables showing all symbols and basic texts that are used with Synco 200. Additionally, all preprogrammed applications are shown as small plant diagrams, to help you to find the required controller and the corresponding number of preprogrammed application.
Content Introduction . Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating elements and symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 List of abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Commissioning . Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction Operating elements and symbols Operating elements 1 Display SERVICE PASS COMMIS INFO PARA PARA SET APPL ID CONF TEST D1 D2 X1 X2 X3 X4 X5 1 2 MODE 3P SET 1 2 3 LIN BIN °F °C K % 2 Navigation buttons – for selecting menu lines or adjusting values 3 OK button – for confirming menu lines or values 4 ESC button – for returning to the previous menu or for rejecting the SERVICE PASS D1 D2 X1 X2 X3 X4 X5 value entered COMMIS INFO PARA 2 MODE 1 SERVICE PASS D1 D2 X1 X2 X3 X4 X5 SET PARA 3P
°C °F %OPEN 0.0 0000 0–10 2xNI 3P 3-POINT A ACCESS ACK ACTING ACTTIME ADAP ALM OFF AO APPL ID CAS/CON CASC CAUTION NEW CH OVER CLOS CLSD CMF CMP1D CMP1END CMP1STT CMP2D CMP2END CMP2STT CNST CO SEQ1 CO SEQ2 CO SEQ4 CO SEQ5 COMMIS CONFIG COOL COOLER CORR CTL1 CTL2 CTLOOP 1 CTLOOP 2 DIFF DIG DIG DLY OFF DMP DV ALM DV DLYH DV DLYL ECO ERC FROST FRST Degrees Celsius Degrees Fahrenheit Outside temp-dependent open Universal 000.
SERVICE PASS D1 D2 X1 X2 X3 X4 X5 COMMIS PASS PASSWRD PASSWRD PRIO CH PRT PT PUMP 1 PUMP 2 PUMP 3 REM1 REM2 ROOM ROOM ROOM TN ROOM XP S V1 S V2 S1-OFF S1-ON S2-OFF S2-ON S3-OFF S3-ON S4-OFF S4-ON S5-OFF S5-ON S6-OFF S6-ON SAT SBIN SEQ SEQ MOD SEQ SEL SEQ SET SEQ XP SEQ TN SEQ1 SEQ1 P SEQ1 TN SEQ1 TV SEQ1 XP SEQ1 Y SEQ2 SEQ2 P SEQ2 TN SEQ2 TV SEQ2 XP SEQ2 Y SEQ4 SEQ4 P SEQ4 TN SEQ4 TV SEQ4 XP SEQ4 Y SEQ5 SEQ5 P SEQ5 TN SEQ5 TV SEQ5 XP SEQ5 Y 6 Password level Enter password Password Run priority changeo
Commissioning Access level overview User level Service level Password level Access to info pages and setpoint menu Access to info pages and setting menus Access to all menus Press OK + ESC Press OK + ESC Press OK + ESC Menu overview (see page 8) Menu overview (see page 10) Press OK Commissioning How to get into the different access levels Select 2 Press OK Menu overview (see page 12) 7
Navigation overview – user level Info pages Info pages show actual values, Setpoint menu SET to define setpoints (see page 18) 8
Commissioning setpoints, fault messages and other user relevant data (see page 20) 9
Navigation overview – service level Info pages Info pages show actual values, Setting menus INFO shows all inputs and outputs (see page 17) 10 PARA to define parameters (see page 16)
Commissioning setpoints, fault messages and other user relevant data (see page 20) SET to define setpoints (see page 18) 11
Navigation overview – password level Info pages Info pages show actual values, Setting menus INFO shows all inputs and outputs (see page 17) Commissioning menus (see page 16) PARA to define parameters 12 SET to define setpoints
Commissioning setpoints, fault messages and other user relevant data (see page 20) PARA to define parameters (see page 16) SET to define setpoints (see page 18) APPL ID to choose an application CONF to define configuration TEST to check inputs and to simulate outputs 13
Getting started 1 How to get into the password protected area 2 How to select a preprogrammed application (APPL ID) Press OK + ESC Info page in the password level Press OK Press OK Setting menus Press OK Press OK Stop the plant Press OK Commissioning menus Select APPL ID Application menu Press OK 14
3 How to start a preprogrammed application Application number Commissioning Press OK, select number, press OK Warning page Press OK Parameter menu (to define parameters see page 16) Press ESC Start the plant Press OK Commissioning menu Press ESC Info page 15
4 How to adjust configuration and settings – How to define parameters (PARA), setpoints (SET), applications (APPL ID) – How to adjust a standard application (CONF) – How to test inputs and outputs (TEST) Menus in COMMIS Parameter menu: Select PARA Press OK …to define parameters Setpoint menu: Select SET (see page 18) Select an input or a function Press OK …to define setpoints Application menu: Select APPL ID (see page 14) Define the heating setpoint Press OK …to select an application Configuration me
5 How to check inputs and outputs (INFO) (only in password or service level) This menu allows you to look up all input and output values to check your plant.
6 How to define setpoints (SET) (in all levels) Info page Press OK Commissioning menu Select SET Press OK Press ESC Press OK Setpoint menu Press ESC Setpoints 18
7 How to protect your settings by selecting the user level Info page in the password level Press OK + ESC Select USER Commissioning Change to the user level Press OK Info page in the user level 19
Info pages overview Number and content of the info pages depend on the loaded application User level Service and Description password level Shows actual room temperature and setpoint Shows actual supply air temperature and calculated setpoint or temperature limits Shows all configured sequences. The active sequence flashes Shows the outside temperature Shows the status of the analog outputs in [V]. Y1=3V, Y2=0V, Y3=not used Shows the status of the relay outputs Q1…Q3. (I=closed, 0=open).
Preprogrammed Applications Air handling applications S01 S01 Air pressure and air quality control B4 AQ Y2 ∆p N.X1 [ppm] M G2 Y1 N.Y1 M Y6 T R5 T M1 B9 S5 APPL ID: U06 f1 f2 N.Q1 N.Y1 R5.1 B7 N.X1 T N.X4 RLU232 R5.2 S5 N.X2 N.D1 APPL ID: U02 AQ Y2 M S01 S01 RLU222 T N.X2 B8 N.X3 ∆p G1 B9 N.X5 N.D1 f2 T N.X4 N.Q1 N.Q2 N.X3 f1 N.Q2 N.Y2 M B4 N.X1 [ppm] Y2 Y1 Y1 N.Y1 M T N.Q2 M1 N.Q3 N.Q1 N.Q4 N.Q5 N.Q6 B9 N.X3 B2 M Y6 N.Y1 M T M M T R5 N.
B5 T T S01 S01 Temperature control: Cooling coil N.X2 Cascade B2 N.X1 T T B9 B1 N.X3 N.X2 R5 T T T N.X4 B9 S5 S5 N.D1 N.D1 RLU202 APPL ID: A05 S01 APPL ID: A06 S01 RLU220 N.X4 N.X1 N.Q1 N.Q2 M Y4 N.Y1 R5 T B1 M7 N.X3 B5 T T N.X2 B2 Cascade N.X1 T B1 N.X3 N.X1 T T R5 T N.X4 B9 Y7 N.X3 N.Y2 M APPL ID: A07 RLU222 APPL ID: A07 S01 RLU220 N.D1 N.Q1 N.Q2 N.D1 N.X4 S5 M7 S5 Y4 N.Y1 R5 T B1 N.X2 T T S01 T B9 B5 N.X2 Cascade B2 N.
T S01 B5 S01 Temperature control: Heating coil, water (1) N.X2 T Cascade B2 N.X1 T T B9 B1 N.X3 N.X1 T R5 T N.X4 N.Q1 N.Q2 N.X4 N.D1 N.Y1 RLU220 APPL ID: A01 S01 S01 APPL ID: A03 N.Q1 S5 Y3 S5 N.D1 RLU202 R5 T B1 N.X2 M M Y3 T B9 N.X3 1 T T B2 B2 N.X1 F3 F3 N.X3 N.X3 1 T T T T N.X2 M M N.D1 N.Y1 S5 Y3 S5 Y3 RLU222 B1 N.X4 N.X2 N.Q2 T T B9 B1 M3 APPL ID: A04 RLU220 APPL ID: A03 S01 N.Q1 N.D1 N.Y1 1 T T S01 B9 N.X4 N.X1 B5 N.
Temperature control: Heating coil, water (2) T B1.1 N.Q1 N.X1 T T M B9 Y3.1 R5.1 N.X2 M3.2 B1.2 N.Q3 N.X3 S01 T M3.1 T M N.Y1 Y3.2 R5.2 N.X4 S5 N.Y2 N.X5 N.D1 RLU232 APPL ID: U01 B5 T T S01 S01 Temperature control: Heating coil, electric N.X2 B2 Cascade N.X1 T T B9 N.X3 E1 N.Q4 N.Q1 N.Q5 N.Q2 N.Q6 N.Q3 N.Y1 R5 T T T N.X4 B1 B9 N.X2 N.X3 S5 E1 B1 N.Q1 N.Q2 N.X1 R5 T N.X4 N.D1 S5 N.D2 N.
S01 S01 Temperature control: Heating + cooling coil, water (1) T B2 N.X1 F3 N.X3 T T T B9 T B1 N.X4 R5 N.X2 N.X1 M Y5 T Y3 F16 M S5 N.Y2 N.D1 N.D1 APPL ID: A09 RLU220 APPL ID: U10 S01 S01 RLU220 Y4 M N.Y1 S5 N.X2 N.Y1 T T B2 B2 N.X1 T T B9 B1 N.X3 N.X2 M R5 T N.X4 T M Y3 Y4 N.Y1 N.Y2 Y3 S5 Y4 M N.Y1 R5 N.X2 M S5 N.Y2 N.D1 N.D1 APPL ID: A10 RLU222 APPL ID: U13 S01 S01 RLU220 N.X1 B5 T N.X2 T Cascade B2 N.X1 B1 N.X1 N.
Temperature control: Heating + cooling coil, water (2) S01 S01 N.Q1 1 T T B2 B5 N.X2 Cascade N.X1 F3 N.X3 1 R5 T T B9 B1 B9 N.X2 N.X4 M3 M4 N.Q1 N.Q2 M M Y3 Y4 N.Y1 N.Y2 T T B1 M3 N.X1 N.Q3 M S5 N.D1 APPL ID: A09 S5 M Y3 Y4 N.Y1 N.Y2 RLU232 N.D1 S6 N.D2 APPL ID: A03 S01 RLU222 T N.X4 S01 N.X3 T B5 T T N.X2 Cascade T T N.X3 M3 M4 N.Q1 N.Q2 M M Y3 Y4 N.Y1 N.Y2 RLU222 R5 T T N.X4 B1 T B9 N.X1 N.X3 N.D1 APPL ID: A10 B1 M3 M4 N.
S01 N.Q1 S01 Temperature control: Heating + cooling coil, DX cooler 1 T T B2 B2 N.X1 N.X1 F3 N.X3 1 T T T B9 M3 N.X4 N.Q2 T B1 Y7 R5 B9 N.Y2 M S6 N.Q3 N.Q4 N.Q5 N.Q6 Y3 N.D2 N.Y1 APPL ID: A07 RLU222 1 T M7 S5 N.Q1 N.Q2 N.D1 APPL ID: A13 S01 N.Q1 N.X4 N.X2 S01 RLU236 N.D1 M7 Y3 R5 T B1 Y7 N.X3 S5 M N.Y1 T T N.X5 N.X2 N.Y2 B5 B5 T N.X2 N.X2 Cascade Cascade F3 N.X3 T T B9 M3 N.X4 N.Q2 T B1 Y7 N.Y2 R5 N.X5 N.D1 Y3 N.Y1 M7 S6 N.Q3 N.
S01 Temperature control: Heating + cooling coil, electric heater T B2 N.X1 T T B9 N.X3 E1 B1 N.Q1 N.Q2 N.Y1 N.X2 N.X4 M S5 Y4 N.D1 N.Y2 APPL ID: A11 S01 RLU222 R5 T B5 T N.X2 Cascade T T B9 N.X3 E1 B1 N.Q1 N.Q2 N.Y1 N.X1 N.X4 M S5 Y4 N.D1 N.Y2 APPL ID: A12 S01 RLU222 R5 T T B2 N.X1 T T B9 E1 N.X3 N.Q1 N.Q2 N.Q3 N.Q4 N.Y1 Y7 N.Y2 T B1 R5 N.X4 N.X2 S5 N.D1 M7 S6 N.Q5 N.Q6 APPL ID: A05 T S01 RLU236 N.D2 B5 N.X2 Cascade T T B9 E1 N.X3 N.Q1 N.
Y1 N.Y2 M Y2 B2 M Y1 N.Y1 M T T B9 N.X3 M3 M7 N.Q1 N.Q2 T R5 Cascade Y6 T T N.X4 B1 B9 N.X2 N.X3 E1 B1 N.Q1 N.Q2 N.X1 M N.D1 N.Y2 APPL ID: A24 RLU222 APPL ID: A29 Y2 B2 M Y1 T T M N.Y2 M M Y1 N.Y1 M T T B9 M7 N.X3 N.Q1 N.Q2 M B5 N.X2 Cascade M N.X1 Y6 T R5 Y6 N.X4 B9 N.X3 N.X2 E1 N.Q1 N.Q2 N.Q3 N.Q4 N.Y3 S5 N.D1 N.Y1 T T B1 Y3 APPL ID: A26 RLU236 Y7 B1 T R5 N.X4 N.X1 N.Y2 S5 M7 S6 N.D1 N.Q5 N.Q6 N.
Temperature control: Heating + cooling coil + heat recovery T B10 B2 N.X4 N.X1 1 T T S01 N.Q1 S01 T B5 N.X2 Cascade B10 N.X5 F3 N.X3 T T B9 B1 Y11 M3 N.Y2 M4 N.Q1 M Y4 N.Y1 N.Y3 RLU232 N.X5 M N.D1 S6 N.D2 Y4 N.Y1 N.Y3 S01 B2 B21 N.X1 N.X4 F3 T T T Y11 M M Y4 N.Y1 N.Y3 N.D1 S6 M M Y3 Y4 N.Y1 N.D2 RLU232 N.X5 S5 N.D1 S6 N.D2 N.Y3 APPL ID: A04 T T B10 S01 S01 APPL ID: A08 R5 N.X2 N.Q1 S5 T B1 M3 N.X3 N.Q3 M T B9 N.
S01 N.Q1 N.X1 F3 Y6 N.X3 1 T T T B1 B9 T M3 N.X2 N.Q2 N.X3 M S5 RLU220 APPL ID: A15 S01 N.Q1 B5 T 1 T N.X2 M Cascade M Y1 N.D1 N.Y1 APPL ID: A21 1 N.Y2 M S5 Y3 N.D1 N.Q1 Y2 T B10 B2 N.X4 N.X1 F3 F3 Y6 N.X3 N.X3 1 T 1 T B9 M3 N.X4 N.Q2 T T B1 B9 N.X1 N.X5 N.X2 N.Q3 N.Y2 N.D1 B1 M3 Y11 S5 N.Y1 T T M S5 Y3 S6 M Y3 N.D1 N.Y1 APPL ID: A22 RLU232 N.D2 APPL ID: A01 N.Q1 S01 RLU222 1 M Y1 N.Y2 M T B2 B10 N.
S01 S01 Humidity control: Dehumidifier φ T B12 B5 T φ T N.X3 B18 N.X1 [%] N.X1 [g/kg] R5 T R5 T N.X3 N.X4 Y7 N.Y1 M N.D1 N.D1 N.Q1 N.Q2 N.X2 APPL ID: U02 RLU222 N.X2 APPL ID: U05 S01 S01 RLU220 S5 M7 S5 Y4 N.Y1 φ φT T T B5 N.X3 B12 N.X1 [%] B18 N.X1 [g/kg] T R5 T N.X3 R5 N.X4 Y7 N.Y1 S5 N.X2 N.Q2 N.Q3 N.Q4 N.Q5 N.Q6 M S5 Y4 RLU236 N.D2 APPL ID: U04 S01 APPL ID: U03 S6 N.Q1 S01 RLU220 N.X2 N.D1 N.Y1 N.D1 M7 B5 T φ T N.X3 B12 N.
φ φ B12 B12 N.X1 [%] N.X1 [%] φ M Y8 S01 S01 Humidity control: Humidifier R5 T φ N.X3 B11 Y8 N.X2 [%] M8 N.Y1 N.Q1 S5 RLU222 APPL ID: U07 S01 APPL ID: U01 N.X3 N.D1 S01 RLU220 N.X4 S5 M7 N.Q2 N.D1 R5 N.X2 [%] N.Y2 N.Y1 T B11 Y7 M φ φ B12 B12 N.X1 [%] N.X1 [%] φ Y8 M R5 Y8 N.X3 M8 R5 N.X4 N.X2 [%] N.Y2 S5 M8 N.D1 N.Q1 N.Q2 M7 N.D1 RLU236 N.D2 N.X3 APPL ID: U07 N.Q1 S01 APPL ID: U01 S6 N.Q3 N.Q4 N.Q5 N.Q6 S5 N.Q1 N.Q2 T B11 Y7 M N.
S01 Temperature and humidity control: Heating + cooling coil + mixing dampers/heat recovery + humidifier φT T B15 B5 N.X3 N.X2 Cascade T φ T B9 Y8 M3 Y11 N.X5 N.Q1 N.Y2 B1 B11 M N.X1 N.X4 N.Y3 M M8 Y3 N.Q3 S5 N.D1 S6 N.D2 N.Y1 RLU232 APPL ID: A12 S01 N.Q1 1 φT M Y2 M Y1 N.Y2 M T B15 B5 N.X4 F3 Y6 N.X2 Cascade N.X3 1 T T T B9 B1 N.X5 N.X1 M M M8 Y3 Y4 N.Q3 N.Y1 N.Y3 N.D1 S6 N.D2 APPL ID: A16 N.Q1 1 φT B15 M6 N.Q3 T B5 S01 RLU232 S5 N.
Applications for Asian and American regions T M B2 Y2 N.X1 Y6 M F1 ∆p T M T B9 Y1 B31 N.X4 N.Y1 T ∆p G1 S5 B7 N.Y1 N.X3 N.X5 Y3 N.D1 APPL ID: U16 RLU232 B1 M S5 N.X2 Y4 M1 N.Y2 N.D1 N.Y3 S6 N.Q1 N.X1 RLU222 T F4 M N.D2 APPL ID: A17 F1 ∆p M G2 T Y2 V N.Y1 B2 B2 Y6 N.X1 N.X1 M F1 R5 T N.X5 S5 T ∆p N.D1 S6 N.D2 S5 N.D1 G1 N.Y2 RLU222 V ∆p B1 B7 N.X2 N.X3 APPL ID: U17 B9 M T Y1 E2 B31 N.Y1 N.X3 T T N.Q3 N.Q4 N.
Heating/Cooling applications T B9 N.X3 B1 T S01 S01 Temperature and differential temperature control N.X1 M4 N.Q2 M S5 Y3 T B1 T N.X2 N.X1 N.D1 N.Q1 N.Q2 M B16 φT Y4 R5 T N.Y1 S5 N.Q1 N.D1 B7 N.X2 APPL ID: U08 RLU202 APPL ID: U06 S01 S01 RLU222 T H1 Y3 T B1 M T N.X4 N.Q1 N.Q2 M B16 φT N.X2 N.X1 Y4 S5 N.D1 R5 T N.Y1 T S5 APPL ID: U09 RLU202 N.Q1 N.Q2 M APPL ID: U07 B6 S01 Y3 B7 N.X1 N.D1 RLU220 N.X2 T N.X1 S5 N.D1 T R5 N.X2 M3 T N.
Differential pressure control, liquid B23 T N.X2 B9 B22 p f1 M11 p N.X1 [bar] N.Q1 N.Q2 N.Q3 N.Q4 S01 N.X3 T f2 G1 R5 B21 N.X1 M7 p N.X4 N.Y1 S5 S5 N.D1 RLU220 N.D1 RLU236 APPL ID: U04 B23 N.X2 N.Q1 f1 B22 ∆p f1 f2 G1 ∆p N.X1 [bar] S01 N.Q2 APPL ID: U18 f2 G2 N.Y2 N.Y1 T R5 N.X4 T B9 S5 N.X3 N.D1 RLU222 APPL ID: U02 B23 B22 ∆p ∆p N.X1 [bar] S01 N.X2 f1 f2 f2 G2 N.Y2 T R5 N.X4 Applications f1 G1 N.Y1 T B9 S5 N.X3 N.
Special applications DC 0 ... 10 V G1 D1 M Q11 Q23 G X1 M G1 D1 M Q11 Q33 Q14 Q34 A01 X1 M A01 G DC 0 ... 10 V RLU232 RLU202 G0 N1 Q12 Q14 N2 G0 Q24 Q12 3P Q1 M Q1 APPL ID: U10 RLU232 G1 D1 M Q11 A01 X1 M Q23 G X1 M RLU202 G1 D1 M Q11 Q33 Q14 Q34 RLU232 G0 N1 Q12 Q14 N2 Q24 G0 Q12 2Q VAR. RLU202 2Q VAR. APPL ID: U11 RLU232 DC 0 ... 10 V APPL ID: U05 DC 0 ...
Q11 Q23 Q33 Q41 Q53 Q63 Q14 Q24 Q34 Q42 Q44 Q54 Q64 A01 X1 M G1 X1 M G1 G RLU236 Q11 Q23 Q33 Q41 Q53 Q63 Q14 Q24 Q34 Q42 Q44 Q54 Q64 RLU236 Q12 G0 Q12 5Q LIN. RLU236 5Q VAR. APPL ID: U10 RLU236 DC 0 ... 10 V X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63 Q14 Q24 Q34 Q42 Q44 Q54 Q64 G RLU236 X1 M G1 Q11 Q23 Q33 Q41 Q53 Q63 Q14 Q24 Q34 Q42 Q44 Q54 Q64 RLU236 Q12 G0 Q12 6Q LIN. RLU236 6Q VAR. APPL ID: U11 RLU236 DC 0 ...
Configuration diagrams RLU202 A only in basic type A U only in basic type U Type A X2 X1 LABEL LABEL LABEL LABEL x x x U y p y p xQ 1 MODE X4 y p y xp Q LABEL x FROST Type A Q y1 y2 DIFF SHIFT MAIN 1 x x x SEQLIM CTLOOP 1 1 y p y p y1 y2 y p y p Q IN X 3 POINT Stufenschalter LIN Stufenschalter BIN PUMP 2 2 3101B03de PUMP 1 PUMP 2 Q Q y1 y2 x CLOSE PUMP 1 1 OPEN STEP 1 STEP 2 3P Q Q Q1 Q2 y1 y2 x STEP V1 Q Q1 Q2 IN X IN X Q 3 POINT Stufensch
RLU220 A only in basic type A U only in basic type U LABEL LABEL x Y X4 LABEL x Y Type U x Y y 1 y y y U x Y x x y1x y2 x SEQLIM CAS/CON X4 LABEL MODE x x FROST Type A Type U x Y y x HREC MECH 2 MAT IN X MODE x x OPMODE x CH OVER x MECH 1 IN X DIFF MAIN x FROST y Y Y y1 y2 LIN Stufenschalter x AO 2 2 1 y1 y2 x x Stufenschalter BIN HREC MECH 2 AO 1 x MECH 1 y1 y2 ....................
RLU222 only in basic type A A U only in basic type U LABEL LABEL x Y X4 Type U LABEL x Y x Y x x LIM SEQLIM CTLOOP 2 2 y p y p Q y p y p LABEL x FROST Type A Q y1 Y1 y2 3101B03de 42 Y1 Y2 HREC x x AO 1 AO 2 HREC MECH 1 MECH 2 Q1 Q2 2 1 x x IN X Cooler Y x Q Q1 Q2 IN X Q Q1 Q2 Q Q Q1 Q2 CH OVER Q MAT 3P x ALM OFF SEQ4 Y SEQ4 P y1 y2 IN X 3 POINT x OPMODE IN X MECH 2 SEQ1 Y SEQ1 P x ....................
RLU232 only in basic type A A U only in basic type U Type U LABEL x Y D1 y p y p CH OVER MODE Q1 Q3 y1 y2 x IN X Y2 Y3 ALM OFF HREC Y STEP 1 STEP 2 A0 3 IN X x Cooler Y y1 y2 x IN X STEP BIN STEP 1 STEP 2 AO STEP 1 STEP 2 A0 STEP 1 STEP 2 A0 Y Q Q Y Q Q Y Y Y1 Y Y2 Y3 Q Q Q1 Q3 x .................... Q Q Y x Y IN X STEP LIN STEP V1 x IN X HREC Y x ....................
RLU236 only in basic type A A U only in basic type U LABEL x Y y p y p MODE Q x Y2 3101B07de A0 3 Y y1 y2 Q Y3 y1 y2 AO 3 2 1 Q Q Q Q Q Q A0 1 Q Q x Q1 Q2 Y Q Y Q Q y1 Q4 y2 Q3 IN X x IN X y1 y2 Q Q5 IN X Y x IN X STEP BIN AO STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 AO STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 AO STEP 1 STEP 2 STEP 3 STEP 4 AO STEP LIN Q Q Y Q Q Q Q Q Q Y Q Q Q Q Q Q Y Q Q Q Q Y Y Y1 Y Y2 Y3 Q Q Q Q Q Q Q1 Q2 Q3 Q4 Q
Notes 45
Notes 46
Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 Siemens Building Technologies Brunel House Sir William Siemens Square, Frimley Camberley Surrey, GU16 8QD United Kingdom Tel +44 1276 696000 Fax +44 1276 696133 Siemens Ltd Building Technologies Units 1006-10 10/F, China Resources Building 26 Harbour Road Wanchai, Hong Kong Tel +852 2870 7888 Fax +852 2870 7880 The information in this document contains gener