User Manual

4-7
Siemens Switzerland Ltd http://www.siemens.com/buildingtechnologies-productcatalog 2015
Building Technologies Division
4
Room automation
Overview and selection tools
Configurable Room Automation Station with BACnet
Fan powered box
Application can be configured from these functions:
Supply air control
External flow control for VAV with integrated flow controller and
differential pressure sensor
Internal flow controller and differential pressure sensor for dam-
per actuator control
Internal flow controller and velocity sensor for damper actuator
control
Single Speed Fan , 2 speed Fan or Variable Speed Fan
Chilled water cooling coil
Heating/Cooling coil
Hot water heating coil
Electric heating coil modulating, single stage or two stage
Room temperature control by two-pipe system with change-over
Room temperature control by four-pipe system
Supply air temperature cascade control
Room air quality control
Rapid ventilation
Green leaf
Primary air temperature
for air after-treatment
(TPaAftrt)
Supply air
VAV
(VavSu)
Extract air
tempera-
ture (TEx)
Mixed air
tempera-
ture (TMx)
Fan speed
(FanSpd)
Cooling
coil
(Ccl)
Heating/
cooling coil
(HCcl)
Heating
coil (Hcl)
Supply air
tempera-
ture (TSu)
DI
AI 1 1 1 1
Relais
Triac 2 1-2 1-2 1, 2, 4, 8 1-2
0..10 V 1 1* 1 1, 4 1**
Actuator for VAV
(KNX PL-Link)
1*
* Requires additional triac for enable signal
** Requires additional triac for electric heating enable signal
Radiant ceiling and Radiator
Application can be configured from these functions:
Chilled ceiling with chilled water
Heated/chilled ceiling by two-pipe system with change-over
Heated/chilled ceiling by four-pipe system with 6 way valves
Heating ceiling with hot water
Hot water radiator
Electric radiator modulating or staged
Downdraft compensation for radiators
Condensation monitor
Room temperature control
Green leaf
Radiator
(Rad)
Radiator
overtemperature
(RadOvrT)
Radiant ceiling
(Rcg)
Condensation monitor
(CdnMon)
DI 1 1
AI
Relais
Triac 1-4 1-4
0..10 V 1-2* 1-2
* Requires additional triac or relais for electric heating enable signal