Data sheet N1661
Operating voltage DC 24 V
AC 24 V
Voltage supply LonWorks bus (LPT10)
Power consumption 0.82 VA
Ambient temperature‚ operation -20…60 °C
Ambient humidity‚ operation <70 % r.H.
Degree of protection IP42
Dimensions (W x H x D) 58 x 78 x 46 mm
Weight 0.173 kg
Stock No. Product No.
S55842-Z100 RXZ95.1/LON
Data sheet N1662
Operating voltage DC 24 V
Voltage supply KNX bus
Power consumption 0.6 VA
Ambient temperature‚ operation -5…45 °C
Ambient humidity‚ operation 5…93 % r.H.
Degree of protection IP20
Dimensions (W x H x D) 71 x 71 x 27 mm
Weight 0.07 kg
Radio frequency receiver with Gateway EnOcean/LonWorks‚ AC / DC 24 V‚
external antenna
Stock No. Product No.
S55842-Z101 RXZ97.1/KNX
V Wireless receiver with LonWorks
®
interface FTT10A
V Evaluation of up to 9 EnOcean room units (room temperature and setpoint adjustment)
Radio frequency receiver with Gateway EnOcean/KNX
For use with:
-Desigo RXC
- Devices / systems with LonWorks
®
communication
An external antenna is included in the delivery.
V Evaluation of up to 32 EnOcean channels
V With RXB‚ other EnOcean functions may also be integrated: switches‚ window contacts‚ motion detec-
tors
V Other EnOcean functions (dimming‚ blinds‚ light sensors) can be realized in KNX systems
V Powered via KNX bus
V With internal antenna
RXZ95.1/LON
RXZ97.1/KNX