User Manual
Room automation
Desigo TRA
Compact room automation stations BACnet/MSTP DXR2.M..
NEW PRODUCT
4-28
2015Some products are not available in every country
www.siemens.com/buildingtechnologies-productcatalog
Siemens Switzerland Ltd
Building Technologies Division
4
Data sheet N9206
Operating voltage AC 230 V
Power consumption 23 VA
Frequency 50/60 Hz
Analog output‚ signal DC 0...10 V
Analog outputs‚ number 3
Analog output‚ current 1 mA
Universal inputs‚ number 2
Relay outputs‚ number 3
Relay output‚ switching voltage AC 250 V
Relay output‚ switching current 4 (3) A
Mounting On DIN rail or wall
Communication BACnet/MSTP
KNX PL-Link
Degree of protection IP20
Dimensions (W x H x D) 112 x 49 x 165 mm
Data sheet N9206
Operating voltage AC 230 V
Power consumption 23 VA
Frequency 50/60 Hz
Analog output‚ signal DC 0...10 V
Analog outputs‚ number 1
Analog output‚ current 1 mA
Universal inputs‚ number 2
Relay outputs‚ number 1
Relay output‚ switching voltage AC 250 V
Relay output‚ switching current 4 (3) A
Triac outputs‚ number 4
Triac output‚ switching voltage AC 24 V
Triac output‚ switching current 150 mA
Mounting On DIN rail or wall
Communication BACnet/MSTP
KNX PL-Link
Degree of protection IP20
Dimensions (W x H x D) 112 x 49 x 165 mm
Stock No. Product No.
S55376-C116 DXR2.M09-101A
Stock No. Product No.
S55376-C117 DXR2.M09T-101A
Compact room automation station‚ BACnet/MSTP‚ 230 V‚ flat housing‚ 1 DI‚ 2 UI‚
3 relay‚ 3 AO
Compact room automation station‚ BACnet/MSTP‚ 230 V‚ flat housing‚ 1 DI‚ 2 UI‚
1 relay‚ 1 AO‚ 4 triac
Compact room automation stations for HVAC‚ lighting‚ and shading:
V BACnet/MSTP communications
V KNX PL-Link bus to connect sensors‚ actuators‚ and operator units (including bus power)
V USB interface for Tool
Compact room automation stations for HVAC‚ lighting‚ and shading:
V BACnet/MSTP communications
V KNX PL-Link bus to connect sensors‚ actuators‚ and operator units (including bus power)
V USB interface for Tool
DXR2.M09-101A
DXR2.M09T-101A