User Manual
4-16
Siemens Switzerland Ltd http://www.siemens.com/buildingtechnologies-productcatalog 2015
Building Technologies Division
4
Room automation
Overview and selection tools
Programmable Room Automation Station with BACnet
Room units and fi eld devices
All room units and other KNX PL-link devices shown in part “Confi gurable room automation station“ can be used also with programmable
room automation station. Additionally, following devices can be used.
Product No. SSN Description
QMX7.E38 QMX7.E38
Touch room operator unit 4.3 inch for use with PXC3.E7.. and DXR2..E..
series room automation station
RXM21.1 S55376-C104
I/O block with KNX PL-Link for use with a PXC3.E7.. series room automation
station
RXM39.1 S55376-C105
I/O block with KNX PL-Link for use with a PXC3.E7.. series room automation
station
RL 513 5WG1 513-4DB23 Binary Output (relay), 3 x AC 230 V, 6 A
RL 260/23 5WG1 260-4AB23 4-fold binary input, AC/DC12…230V
UP 255D21 5WG1 255-2DB21 Brightness sensor
PXC3.E16A-100A S55376-C118 BACnet / IP - DALI Gateway
Compact room automation station with BACnet
Communication
BACnet/IP DXR2.E09-101A DXR2.E09T-101A DXR2.E10-101A DXR2.E12P-102A DXR2.E18-1..A
BACnet MS/TP DXR2.M09-101A DXR2.M09T-101A DXR2.M10-101A DXR2.M11-101A DXR2.M12P-102A DXR2.M18-1..A
System functions (BACnet)
BACnet profi les B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC
Programming
n n n n n n
Housing
DIN
n n n
Flat
n n n
Operating voltage
230V
n n n
24V
n n n
Inputs and outputs onboard
Digital inputs 1 1 1 1 1 2
Universal inputs 2 2 2 2 2 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 8
Analog outputs
(DC 0…10 V)
3 1 2 2 4
Pressure sensor 1
Maximum confi guration
Total data points 30 30 30 30 30 60
Integrated power
supply for KNX (mA)
50 50 50 50 50 50