User Manual
7
Siemens
Data sheet
A6V10446174_en--_f
Smart Infrastructure
2020-09-01
Technical data
Power supply
Operating voltage
Tolerance
AC 230 V
+10 %/-15 %
Frequency
50/60 Hz
Power consumption
6 VA at 50 Hz (when running only)
Primary fuse or breaker rating
External, 2 A quick blow
Signal input
Control signal
2-position (SPST)
1)
Parallel operation
Permitted
2)
1)
Phase cut and pulse-duration-modulated (PDM) signals are not suitable, 3 position operation not permissible,
SPST = Single Pole, Single Throw
2)
Consider controller’s output power
Operating data
Position with de-energized contact Y
See "Technical design [➙ 2]"
Positioning time (open/close)
10 s at 50 Hz
8.3 s at 60 Hz
Positioning force
170 N
Nominal stroke
2.5 mm
Permissible temperature of medium in the connected
valve
1...110 ℃
Electrical connection
Connecting cable (integral)
3-core, 0.8 m
3 x 0.75 mm
2
(18 AWG)
Mounting
Fixing on valve
Plastic union nut M30 x 1.5
Orientation
Upright to 90°, horizontal; do not suspend
Standards
EU conformity (CE)
A6V10634158
Housing protection degree
IP 40
Protection class
II Class as per EN 60730-1
Environmental compatibility
The product environmental declaration (A6V10634107)
contains data on environmentally compatible product
design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
Housing color
Cover/base
Plastic / light gray, RAL 7035
Union nut
Silver-gray, RAL 7001