Integrated Motor/Inverter Installation and Commissiong Instructions
6. Specifications English
© STÖBER plc 1997
29
05.02.01
6. SPECIFICATIONS
CSA-single-phase device
Model PM25/1 PM37/1 PM55/1 PM75/1
Motor frame size: 4 pole 71K 71L 80K 80L
Motor output rating: 0.25 kW 0.37 kW 0.55 kW 0.75 kW
Operating input voltage: 1ø AC 208 - 240 V
rms
± 10%
Operating input frequency: 47 - 63 Hz
Output frequency: 0 - 150 Hz
Output frequency with.
OPm2 or serial link: 4 pole
0 - 140 Hz
0 - 140 Hz 0 - 140 Hz 0 - 140 Hz
Input current: 3.2 A
rms
4.6 A
rms
6.2 A
rms
8.2 A
rms
Main fuse: 10 A 16 A
Min lead cross-section:
1 mm
2
1.5 mm
2
CSA-three-phase device
Model PM37/3 PM55/3 PM75/3 PM110/3 PM150/3
Motor frame size: 4 pole 71L 80K 80L 90S 90L
Motor output rating: 0.37 kW 0.55 kW 0.75 kW 1.1 kW 1.5 kW
Operating input voltage: 3ø AC 380 - 480 V
rms
± 10% (all units) 3ø AC 460 - 500 V
rms
± 10% (unfiltered only)
Operating input frequency: 47 - 63 Hz
Output frequency: 0 - 50 Hz
Output frequency with.
OPm2 or serial link: 4 pole 140 Hz 140 Hz
140 Hz
140 Hz 140 Hz
Input current: 2.2 A
rms
2.8 A
rms
3.7 A
rms
4.9 A
rms
5.9 A
rms
Main fuse: 10 A
Min lead cross-section:
1 mm
2
CSB-three-phase device
Model PM220/3 PM300/3 PM400/3 PM550/3 PM750/3
Motor frame size: 4 pole 100K 100L 112M 132S 132M
Motor output rating: 2.2 kW 3.0 kW 4.0 kW 5.5 kW 7.5 kW
Operating input voltage: 3ø AC 380 - 480 V
rms
± 10% (all units) 3ø AC 460 - 500 V
rms
± 10% (unfiltered only)
Operating input frequency: 47 - 63 Hz
Output frequency: 0 - 50 Hz
Output frequency with.
OPm2 or serial link: 4 pole 140 Hz 140 Hz 140 Hz 140 Hz 140 Hz
Input current: 4.7 A 6.4 A 10.0 A 12.2 A 16.0 A
Main fuse: 10 A 16 A 20 A
Min lead cross-section:
1 mm
2
1.5 mm
2
2.5 mm
2