Data Sheet for Product
General ambient
conditions
Operation
EN 60721-3-3
Transport
EN 60721-3-2
Storage
EN 60721-3-1
Environmental conditions
Class 3K3
Class 2K3
Class 1K3
Temperature
1...50 °C
-25...70 °C
-5...50 °C
Humidity
5...85 % r.h.
< 95 % r.h.
5...95 % r.h.
Connecting cable
7
White
Y2
Control signal CLOSE (AC 230 V)
6
Black
Y1
Control signal OPEN (AC 230 V)
4
Blue
N
Neutral
L = 2,5 m, or 4,5 m
7
Orange
Y2
Control signal CLOSE (AC 24 V)
6
Violet
Y1
Control signal OPEN (AC 24 V)
1
Red
G
System potential AC 24 V
L = 2,5 m, or 4,5 m
8
Grey
Y
Control signal DC 0...10 V
2
Black
G0
System neutral (- DC 24 V)
1
Red
G
System potential AC 24 V (+ DC 24 V)
L = 2,5 m, or 4,5 m
Connection terminals
4891Z
32
Y2
Y1
G
4864Z15
Control signal CLOSE
Control signal OPEN
System potential AC 24 V
48
91Z3
1
G0
Y
G
4864Z16
System neutral
Control signal DC 0...10 V
System potential AC/DC 24 V
Factory setting:
0...50 % Q11 → Q12
50...100 % Q11 → Q14
The switching point can be adjusted by turning the switching cam with a screwdriver
(see Mounting Instructions).
Recommended connecting cable: H03VV-F, 2x0.5…0.75 mm
2
.
ASY3L.. with SSB31..
ASY8L.. with SSB81..
ASY6L.. with SSB61..
ASY99
for SSB81..
ASY10
0
for SSB61..
Terminals for auxiliary
switches
SSB31.1, SSB81.1
7/10
Siemens Electromotoric actuators CA1N4891en_02