Data Sheet for Product

Technical data
SSB31..
SSB81..
SSB61..
Power supply
Operating voltage
Voltage tolerance
AC 230 V
± 15 %
AC 24 V
± 20 %
AC 24 V or DC 24 V
± 20 %
± 25 %
Rated frequency
50 / 60 Hz
Max. power consumption
6 VA
0.8 VA
2.5 VA
Fuse for incoming cable
2 A, quickblow
Control
Control signal
3-position
DC 0...10 V
Input impedance for DC 0...10 V
> 100 kOhm
Parallel operation (number of actuators)
1)
max. 6
max. 24
max. 10
Functional data
Run time for 5.5 mm stroke at 50 Hz
150 s
75 s
Positioning speed
27.3 s/mm
13.6 s/mm
Nominal stroke
5.5 mm
Nominal force
200 N
Perm. temperature of
medium in the connected valve
1...110°C
Electrical connections
Connecting cable of basic types
1.5 m 3-core to EN 60320 / IEC 60227
ASY 99, ASY100 cable diameter
wire cross section
< 5 mm
0.5…0.75 mm
2
ASY3L.. wire cross section
0,75 mm
2
ASY6L.., ASY8L.. wire cross section
0,5 mm
2
Norms and directives
Electromagnetic compatibility
(Application)
For residential, commercial and light- industrial
environments
Product standard
EN60730-x
EU Conformity (CE)
A5W90000895
2)
A5W90000897
2)
A5W90000896
2)
RCM Conformity
A5W90000910_A
2)
A5W90000922_A
2)
A5W90000921_A
2)
EAC Conformity
Eurasia Conformity
Protection class to EN 60730
II
III
Contamination level
EN 60730, Class 2
Housing
protection
Upright to horizontal
IP40 to EN 60529
UL approbation
UL 873
cUL approbation
C22.2 No. 24-93
Environmental compatibility
The product environmental declaration CE1E4891en01
2)
contains data on environmentally compatible product
design and assessments (RoHS compliance,
materials composition, packaging, environmental
benefit, disposal).
Dimensions / weight
Dimensions
refer to «Dimensions», page 9
Coupling thread to valve
union nutinch
Weight with / without auxiliary switch
0.4 kg / 0.35 kg
Housing colors
Base and cover
RAL 7035 light gray
Auxiliary switch
Mounted in SSB31.1 and SSB81.1
1 change-over switch
Switching point adjustable
Factory setting 50 %
0...100%
Switching capacity
3)
max. AC 250 V, 1 A (0.5 A)
Connecting cable (recommended)
H03VV-F, 2x0.5…0.75 mm
2
1)
Provided the controllers’ output is sufficient
2)
The documents can be downloaded from http://siemens.com/bt/download
3)
SSB81, in installations according to UL standards, AV 24 V, 1 A (0.5 A)
6/10
Siemens Electromotoric actuators CA1N4891en_02