User Manual
2 / 10
Siemens CE1N2700en
Smart Infrastructure 2020-05-11
Use
· For integration into the Siemens Synco living system
· Suited for use in heating plant for operating radiator valves from Siemens or radiator
valves of other manufacture
· Several radiator control actuators can be used in one room
Compatibility
The SSA955 is suited for use with the following types of radiator valves from Siemens:
Type reference Valve type k
vs
PN class Data Sheet
[m
3
/h] no.
VDN.., VEN.., VUN.. Radiator valves 0.25…1.41 PN10 2105, 2106
VD…, CLC… Radiator valves 1.9…2.6 PN10 2103
VPD…, VPE… MCV radiator valves 0.02…0.48 PN10 2185
VD…, VE…, VU… Radiator valves 0.25…3.4 PN10 2145, 2146
2T../A Radiator valves 1.25…2.5 PN10 4848
For radiator valves with AV… adapters, refer to "Accessories"
k
vs
= nominal flow rate of chilled water (5…30 °C) through the fully opened valve (H
100
) at a differential
pressure of 100 kPa (1bar)
The SSA955 can operate without adapter radiator valves of other manufacture provided
they have a connecting thread M30x1.5 mm and meet the following requirements:
Requirements placed on valves of other manufacture:
Force 100 N nominal
Fully closed x > 9.0 mm
Fully open y £ 14.5 mm
90187
y
A
F
M30 x1.5
x
AB
The following makes satisfy these requirements and can be used with the SSA955:
· Honeywell MNG
· Cazzaniga
· Heimeier
· TA
· Finimetall
· Oventrop M30x1.5 (from 2001)
· Junkers
Other combinations on request.
To ensure optimum control performance, the valve’s volumetric flow should not be
preadjusted.
If preadjustments are required, refer to the relevant technical documentation on the
valves for detailed information. The SSA955 supports valves with a stroke of > 0.5 mm
(refer to paragraph “Calibration”).
Siemens valves
Valves of other
manufacture
without adapter
Valve preadjustment /
kv limitation