Technical data
Power supply
Battery type 2 x alkaline batteries LR6 (AA) 1.5 V
Battery life 2 years
Radio communication
Frequency range 2.4…2.4385 GHz
Max. transmission power 3.5 dBm
Range ≤ 30 m, depending on application and building
Protocol THREAD, 6LoWAN IEEE802.15.4
Actuator
Stroke nominal 2.5 mm
minimal 0.5 mm
Positioning force typically 90 N
Noise level EN ISO 3741
< 30 dBA
Built-in temperature sensor
Sensing element NTC 4.7 kΩ resistor
Measuring range 0…50 °C
Internal controller
Type PI
Degree of protection
Protection class Class III according to IEC 60730-1
Protection degree of housing IP 30
1)
according to IEC 60529
Pollution degree Class 2 according to IEC 60730
Environmental conditions
Operation
Temperature -20…54°C
Humidity (non-condensing) 65 % r.h. ± 20 %
Transportation
Temperature -30...45 °C
Humidity 65 % r.h. ± 20 %
Storage
Temperature -30...45 °C
Humidity 65 % r.h. ± 20 %
Medium temperature permissible in connected valve 1…70 °C
Directives and standards
Product standard IEC 60730-x
Electromagnetic compatibility (field of use) For residential, commercial, and industrial environments
EU conformity (CE) A5W00090263A
2)
EAC compliance Eurasian compliance for all SAY..P..