Install Instructions
599 Series Zone Valves
Installation Instructions
Document No. 129-346
August 8, 2005
SSA/P Electronic Zone Valve Actuator
24 Vac 3-Position or 0 to 10V Control
Fail-in-Place
Item Number 129-346, Rev. 020 Page 1 of 4
Product Description
The SSA/P actuator requires 24 Vac, Class 2 power, and
a 0 to 10 Vdc or three-position control signal to control
599 Series Zone Valves with 1/10-inch (2.5 mm) stroke.
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not follow a
procedure as specified.
CAUTION:
Equipment damage, or loss of
data may occur if you do not
follow the procedures as
specified.
Product Numbers
Description
Actuator
Code
SSA81U Normally Closed 3-Position 244
SSA61U Normally Closed 0 to 10 Vdc 245
SSP61U Normally Open 0 to 10 Vdc 248
Contents: One actuator
Required Tools
• Small flat-blade screwdriver
• Wire stripper
Estimated Installation Time
20 minutes
Prerequisites
WARNING:
If mounting the actuator to a valve already
in line:
Close the shut-off valves in the piping
(upstream first, then downstream);
Or
Switch off the pump to allow the
differential pressure in the valve to
drop.
Figure 1. Acceptable Mounting Positions. *
*The vertical position is recommended for mounting.
WARNING:
Disconnect the controller power before
replacing the actuator.