Data Sheet for Product

8
Siemens
A6V11858278_en
--
_c
Smart Infrastructure
2021
-
08
-
NOTICE
The actuator must be commissioned only with a correctly mounted valve in place!
Self-calibration
When operating voltage is applied, the actuator self-calibrates (fully retracted fully
extended setpoint).
CAUTION
Never intervene manually during self-calibration.
NOTICE
Correct calibration is only possible with valve stroke > 1.2 mm. Valve stroke < 1.2 mm
results calibration failure.
If calibration fails, the actuator performs another calibration automatically after
10 seconds.
After three failed calibration attempts, the actuator stem remains in the extended posi-
tion and the valves are closed.
Manual operation
A 3-mm hexagonal socket wrench can be used to move the actuator to any position.
To move the actuator stem manually
1. Open the cover using a proper screwdriver. Note that IP54 protection does not apply if
the cover is open.
2. Press and hold down button (a) illustrated below for at least three seconds.
The actuator ignores any control signal from the controller.
3. Adjust the position of the actuator stem by rotating hexagon socket (b) illustrated below
clockwise or anti-clockwise.
The actuator stem moves down if you rotate clockwise; it moves up if you rotate anti-
clockwise. The manually set position is retained.
4. Press and hold down button (a) illustrated below again for at least three seconds.
The actuator runs a self-calibration automatically. Control signal sent from the con-
troller takes effect.
5. Close the cover to ensure IP54 protection.