User Manual
10
Siemens
A6V11858278_en--_a
Smart Infrastructure
2020-07-30
Technical data
Power supply
Operating voltage
AC 24 V (± 15 %) or DC 24 V (± 20 %)
Frequency
50/60 Hz
Power consumption
Running
2.5 VA
Holding
2 VA
Primary fuse or breaker rating
External, 2 A quick blow
Signal input
SSA151.05HF
SSA161.05HF/SSA161E.05HF
Control signal
4…20 mA
DC 0...10 V
Input impedance
150 Ohm
100 kOhm
Parallel operation (number of actuators)
1
Max. 10
1)
1)
Provided that the controller output is sufficient.
Signal output
SSA151.05HF
SSA161.05HF/SSA161E.05HF
Feedback signal
4…20 mA
DC 0...10 V
Max. output current
-
1 mA
Max. output voltage
24 V
-
Resolution
1:100
1:100
Operating data
Position with de-energized contact Y
See "Technical design [➙ 2]"
Running speed
<10 s/mm
Positioning force
100 N
Stroke
1.2…6.5 mm
Permissible temperature of medium in the connected
valve
1...110 °C
(1...90 °C for MCV-radiator valves)
Electrical connection (connecting cable integral)
Cable length (integral)
1.5 m, according to VDE 0207
Cross section of prewired connection cables
0.34 mm
2
(5 ×)
Permissible length for signal lines
20 m
Mounting
Fixing on valve
Plastic coupling nut M30 × 1.5
Orientation
360°
Standards
EU conformity (CE)
A5W00106106A
RCM conformity
A5W00106107A
Housing protection degree
IP 54
Protection class according to EN 60730
III
Environmental compatibility
The product environmental declaration
(A5W00109220A) contains data on environmentally
compatible product design and assessments (RoHS
compliance, materials composition, packaging,
environmental benefit, disposal).