Data Sheet for Product

7
Siemens
A6V11858278_en
--
_c
Smart Infrastructure
2021
-
08
-
Orientation
Installation
A [mm] B [mm] C [mm]
5.5 4.2 50
Crimp ferrule on stripped wire of connecting cable.
Observe all admissible temperatures (see “Technical data [ 11]”).
Do not twist the cable.
Magnets can damage the actuator.
Provide a means for isolation from the power supply, e.g., connecting a circuit breaker or
switch fuse upstream of the control unit.
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
CAUTION
Phase cut and pulse-duration-modulated (PDM) signals are not suitable.
Regulations and requirements to ensure the safety of people and property must be
observed at all times!
Commissioning
When commissioning, check both wiring and functioning of the actuator.
Actuator stem extends Valve closes
Actuator stem retracts Valve opens