Technical data
Power supply
Operating voltage AC 24 V (± 15 %) or DC 24 V (± 20 %)
Frequency 50/60 Hz
Power consumption Running 2.5 VA
Holding 2 VA
Primary fuse or breaker rating External, 2 A quick blow
Signal input SSA151.05HF SSA161.05HF/SSA161E.05HF
Control signal 4…20 mA DC 0...10 V
Input impedance 150 Ohm 100 kOhm
Parallel operation (number of actuators) 1 Max. 10
1)
1)
Provided that the controller output is sufficient.
Signal output SSA151.05HF SSA161.05HF/SSA161E.05HF
Feedback signal 4…20 mA DC 0...10 V
Max. output current - 1 mA
Max. output voltage 24 V -
Resolution 1:100 1:100
Operating data
Position with de-energized contact Y
See "Technical design [▶ 2]"
Running speed <10 s/mm
Positioning force 100 N
Stroke 1.2…6.5 mm
Permissible temperature of medium in the connected
valve
1...110 °C
(1...90 °C for MCV-radiator valves)
Electrical connection (connecting cable integral)
Cable length (integral) 1.5 m, according to VDE 0207
Cross section of prewired connection cables 0.34 mm
2
(5 ×)
Permissible length for signal lines 20 m
Mounting
Fixing on valve Plastic coupling nut M30 × 1.5
Orientation 360°