User Manual
4
Siemens
A6V11858276_en--_a
Smart Infrastructure
2020-07-30
* Nominal volume flow at 0.5 mm stroke.
Note: To ensure trouble-free operation of
third-party valves with the SSA.. actuator,
the valves must satisfy the following
requirements:
● Threaded connections with coupling nut
M30 × 1.5.
● Nominal force F ≤ 100 N
● Dimension X ≥ 8.3 mm
● Dimension Y ≤ 14.8 mm
Controllers
Type
SSA131.00
SSA331.00
SSA161.05
AC 24 V
AC 230 V
AC/DC 24 V
3-position
3-position
DC 0...10 V
DXR2
DXR2..09T.., DXR2..10.., DXR2..11..,
DXR2..12P.., DXR2..18..,
DXR2..10PL..
-
DXR2..09..
RXB..
RXB21.1.., RXB24.1..
-
RXB39.1..
Synco 700
Synco 200
RMH760B-1, RMK770-1, RLU202,
RLU222
-
RMU7...0B-1, RMS705B-1, RMH760B-1,
RMK770-1, RLU220, RLU222, RLU232,
RLU236
Room thermostats
Type
SSA131.00
SSA331.00
SSA161.05
RDG..
RDG405KN
RDG100KN, RDG100, RDG100T
RDG160KN, RDG160T, RDG405KN
RDF..
-
RDF800KN, RDF800KN/NF, RDF302,
RDF600, RDF600T, RDF600KN
-
RDU..
-
-
RDU340
RCU..
-
-
RCU50..
Product documentation
Topic
Title
Document ID:
Mounting and installation
Mounting instructions
1)
A6V11858272
Standards and directives
CE declarations
A5W00106106A
RCM conformity
A5W00106107A
Environmental compatibility
Environmental declarations
A5W00109220A
1)
The mounting instructions is enclosed in product packaging.
Related documents such as environmental declarations, CE declarations etc., can be
downloaded from http://siemens.com/bt/download.
Notes
Engineering
The actuators must be electrically connected in accordance with local regulations (see
"Connection diagrams [➙ 10]”).