Data Sheet for Product

4
A6V11858280_en
--
_b
Smart Infrastructure
2021
-
08
-
06
Protection against unintended KNX programming button pressure
The actuator provides a mechanical function to prevent accidental pressure of the KNX pro-
gramming button.
NOTICE
Fully align A and B illustrated in Step 5 when reassembling the actuator.
Addressing and bus test with the KNX programming button
Press the KNX programming button (< 2 s) to set the actuator to addressing/programming
mode:
KNX bus wiring OK LED turns red until addressing/programming is finished.
KNX bus wiring not OK LED stays off.
Reset using the KNX programming button (master reset)
Reset the actuator by pressing the KNX programming button for more than 20 s. The LED
flashes yellow and the device restarts. All parameters are then reset.
LED colors and patterns
Stem position indicator
Color Pattern Flashing interval Description
Green Flashing 0.1 s Self-calibration
0.5 s Actuator stem is moving.
Constant - Actuator stem reaches a set position. The
LED turns off after it is constantly on for five
seconds.
Green/red Flashing 0.5 s Manual operation
Red Constant - Error*