Commissioning Instructions
Table Of Contents
8
Siemens
A6V12066162_en
--
_b
Smart Infrastructure
2021
-
08
-
06
Objects Range Description
1 = True
position specified by the local or remote override. Any
"Setpoint position" is ignored until the override is
complete, in which case this object receives value “0”
and the actuator resumes normal operation. If the
"Emergency mode" object was set to “1” before the
local/remote override occurs, it is resumed once the
override process is completed.
Emergency mode 0 = No alarm
1 = Alarm
This object sends an alarm telegram if no new actuating
value is received via the bus during a defined period. In
case of no new actuating values, the actuating value to
be approached can be parametrized to "Backup position"
or "Keep last position" under "Valve actuator" →
"Standard settings" → "Reception of valve position
setpoint" at the "Parameter" page. This object is only
available if the "Backup timeout" parameter at the same
location has been activated.
Start calibration 0 = trigger (0)
1 = trigger (1)
This object receives either value “0” or “1”. The actuator
maps the end position of the actuator to the valve and
goes back to the control mode.
Calibration mode 0 = False
1 = True
This mode indicates that the actuator is being calibrated
to find the end position of the valve.
Window contact 0 = close
1 = open
This object sends potential-free input window contact
state “DI1”, if used. The state is sent out periodically or
upon change. If this object is linked with the "Forced
position" object in a group address, the actuator drives
the valve to the specified forced position (by receiving
value “1” in the defined forced position). This object is
available only if window contact “DI1” was activated
under "External interface" at the "Parameter" page.
Condensation contact 0 = No alarm
1 = Alarm
This object sends potential-free input condensation
contact state “DI2”, if used. The state is sent out
periodically or upon change. If this object is linked with
e.g. the Comfort mode object of the controller in a group
address, the actuator acts as an extension of the Comfort
operating mode. This object is available only if
condensation contact “DI2” was activated under "External
interface" at the "Parameter" page.