Commissioning Instructions
Table Of Contents
6
Siemens
A6V12066162_en
--
_b
Smart Infrastructure
2021
-
08
-
06
No. Name in ETS Object
function
Flags Data point type KNX Range
C R W T U ID DPT_Name Format
2 Fault state Transmit 1 1 0 1 0 1.005 alarm 1 bit 0 = No alarm
1 = Alarm
3 Fault transmission Receive 1 0 1 0 1 1.003 enable 1 bit 0 = Disable
1 = Enable
4 Setpoint position Receive 1 0 1 0 1 5.001 scaling 1 byte 0...100 %
5 Forced position Receive 1 1 1 0 1 1.003 enable 1 bit 0 = Disable
1 = Enable
6 Actual position Transmit 1 1 0 1 0 5.001 scaling 1 byte 0...100 %
7 Maximum position Transmit /
Receive
1 1 1 1 0 5.001 scaling 1 byte 0...100 %
8 Summer mode Receive 1 0 1 0 1 1.003 enable 1 bit 0 = Disable
1 = Enable
9 Night mode Receive 1 0 1 0 1 1.003 enable 1 bit 0 = Disable
1 = Enable
10 Office mode Receive 1 0 1 0 1 1.003 enable 1 bit 0 = Disable
1 = Enable
11 Overridden Transmit 1 1 0 1 0 1.002 boolean 1 bit 0 = False
1 = True
12 Emergency mode Transmit 1 1 0 1 0 1.005 alarm 1 bit 0 = No alarm
1 = Alarm
13 Start calibration Receive 1 0 1 0 0 1.017 trigger 1 bit 0, 1 = trigger
14 Calibration mode Transmit 1 1 0 1 0 1.002 boolean 1 bit 0 = False
1 = True
15 Window contact Transmit 1 1 0 1 0 1.019 window/door 1 bit 0 = close
1 = open
16 Condensation contact Transmit 1 1 0 1 0 1.005 alarm 1 bit 0 = No alarm
1 = Alarm
Objects Range Description
Fault information [0...255 ] = Log Nr.
[0...2] = Alarm priority
[0...14] = Application area
[0...4] = Error class
[0...7] = Attributes
[0...7] = Alarm state
Alarm information on the actuator. There are two types of
alarms:
1. Mechanical failure/jam
2. Calibration failure
Fault state 0 = No alarm
1 = Alarm
Indicates if there is an alarm in the actuator.
Fault transmission 0 = Disable
1 = Enable
Enables or disables transmission of "Fault information"
and "Fault state".
Setpoint position 0...100 % Via this object, the set actuating value (0…100 %) is
received via bus, approaching the corresponding "Actual
position". The object needs to be connected to default
group address 30/0/26 (0xF01A).