Mode Description Define Telegram
ErrorCodeSupport = 12 = 0C
Alarm state InAlarm / Locked = 05
Calibration error
Mode Description Define Telegram
S-Mode Log number 02 PID=51: AlarmInfo: 02 01
01 03 0C 05
Alarm priority Medium = 01
Application area System & function of common
interest = 01 dec = 01 hex
Error class Actuator fault = 03
Attributes AlarmTextSupport +
ErrorCodeSupport = 12 = 0C
Alarm state InAlarm / Locked = 05
No alarm (HB repeat every 30 min)
In case of no alarm indication, the following telegram is sent at an interval of 30 minutes:
Time stamp IA Group
address
Command Data Frame
2019/9/24
12:42:16:27
0.2.1 30/3/250
A_GroupValue
_Write
80 00 03 00 00
00 00
b8 e0 02 01 f3 fa 07 00 80
00 03 00 00 00 00
Release alarms
When an alarm occurs, calibration movement can be triggered via KNX command or manual
override mode entered via alarm release button. The alarm occurs again if another failure
(e.g., mechanical jam) exists.
Application
Fields of application
Connect the actuator to the valve and integrate it in a KNX S-Mode system containing other
KNX devices (integration with ETS and freely programmable). It can be used with controllers
(central functions) controlling the water or chilled water supply to groups and/or single
rooms.
Equipment combinations
KNX-certified HVAC controllers may be connected to all KNX devices with compatible
KNX S-Mode data points.