06
Engineering and commissioning
System environments
NOTICE
Good knowledge about KNX networks and tool operation (depending on the system envi-
ronment) is required.
To connect a PC with USB interface to a KNX network, an interface converter (e.g. OCI700,
contained in OCI700.1) is required.
Supported system/network environment and available engineering and commissioning tools
are:
System environment Engineering and commissioning tools
KNX S-Mode ETS5
KNX PL-Link ABT Site 4.1.1 or higher
Engineering
Documentation of engineering
It is highly recommended to document all planning data and settings in a way that is easily
accessible after a long time. This should be especially noted if parameter calculation or
plant-specific adaptations have to be made during engineering and commissioning. For
KNX LTE-mode systems, the engineering and commissioning protocol C3127 ([15]) is avail-
able. For KNX S-Mode systems, this functionality can be covered by ETS.
KNX S-Mode engineering
See Parameters and objects in KNX S-Mode [ 5] for information about parameters and
KNX S-Mode objects.
Controllers should be KNX-certified so that the usual ETS workflows in KNX projects can
apply.
For KNX S-Mode engineering, the required product data (*.knxprod) have to be downloaded
from the Siemens website and imported into the ETS device catalog. To obtain the product
data, navigate to www.siemens.com/hvac-td or www.siemens.com/openair and locate the
“Downloads” section.
KNX PL-Link engineering
All engineering and commissioning work is done via the controller (room automation station),
using ABT Site. ABT Site is never connected directly to an actuator.
Commissioning
Before commissioning, mount the actuator onto the valve using the correct adapter ring and
apply bus voltage. The self-calibration starts automatically afterwards.
KNX S-Mode commissioning
Before KNX S-Mode commissioning, connect the device to KNX bus via the included bus
connection terminals.
To integrate in KNX S-Mode devices, the usual S-Mode commissioning procedures apply to
ETS5. The HMI conforms to the KNX standard. Briefly pressing the key opens device pro-
gramming mode.
Download the ETS application file (.knxprod) from the GAMMA-TD page
(www.siemens.com/gamma-td). After downloading the application to the actuator, it is avail-
able for KNX S-Mode communication.