Condensation contact
Parameters Description
Cyclical transmission Defines if and how often the state of the connected condensation
contact is sent.
No cyclical transmission: Send only when the state changes.
Every x min: The state is sent at intervals of x min.
Minimum repetition time Defines the minimum interval for sending state changes. Upon
frequent state changes, the parameter helps prevent bus traffic
congestion.
Condensation Defines whether a normally closed contact (NCC) or a normally
opened contact (NOC) is used as condensation contact.
NOTICE
"Condensation contact" is displayed in ETS regardless of the device connected to DI2 of
the actuator. If, e.g., a presence detector is connected to DI2, "Condensation contact" dis-
played in ETS indicates presence.
Mode priorities
If different modes are triggered at the same time, the priorities are as follows (if applicable):
Priorities Communication
1 Override control mode
2 Calibration mode
3 Decalcification
4 Forced mode
5 Summer mode
6 Setpoint
7 Emergency mode
If, e.g., forced mode is triggered when the actuator is in summer mode, the actuator enters
forced mode. After forced mode is released, the actuator reenters summer mode.