Commissioning Instructions

10
Siemens
A6V12066162_en
--
_b
Smart Infrastructure
2021
-
08
-
06
Parameters Description
Backup mode
Defines the valve position when no "Setpoint position"
("Emergency mode") is received. As soon as a new actuating
value is received, the new position is assumed. This parameter is
displayed only if a value larger than 0 min is selected for “Backup
timeout”.
Backup position: The valve is driven to a predefined position.
This position is adjustable by dragging the value bar below.
Keep last position: The valve is driven to the last position re-
ceived.
Backup position
Predefined but customizable position the valve can be driven to in
"Emergency mode". This parameter is displayed only if a value
larger than 0 min is selected for “Backup timeout”.
Cyclical transmission of
emergency mode
Defines the transmission time for emergency mode:
No cyclical transmission: No period transmission of the emer-
gency mode. The state is transmitted only if changed.
x min: Time interval of emergency mode state transmission.
Advanced settings
Parameters Description
Valve position Predefined but customizable valve position when "Forced mode"
is activated.
Automatic
decalcification function
Activates the valve protection function.
Inactive: Valve protection is not executed.
Active: The valve is fully opened and closed once if the valve
position has not changed for 7 days.