Specifications

Technical Instructions OpenAir GMA Series, Spring Return, 62 lb-in Rotary, Electronic Damper Actuators
Document Number 155-315P25
January 26, 2011
Page 4 Siemens Industry, Inc.
Agency Certification,
continued
Conformity
Low voltage directive (LVD) 2006/95/EC
EN 60 730-2-14
(Type 1)
Electromagnetic compatibility (EMC) 2004/108/EC
Immunity for all models, except GMA132.xx EN61000-6-2
Immunity for GMA132.xx EN61000-6-1
Emissions for all models EN61000-6-3
Auxiliary Features
Control signal adjustment
Offset (start point) Between 0 to 5 Vdc
Span Between 2 to 30 Vdc
Dual auxiliary switches
AC rating (standard cable) 24 to 250 Vac
AC 6A resistive
AC 2A general purpose
AC rating (Plenum cable) 24 Vac
AC 4A resistive
AC 2A general purpose
DC rating (Standard/Plenum cable) 12 to 30 Vdc
DC 2A
Switch Range
Switch A 0° to 90° with 5° intervals
Recommended range usage 0° to 45°
Factory setting
Switch B 0° to 90° with 5° intervals
Recommended range usage 45° to 90°
Factory setting 85°
Switching hysteresis
WARNING:
Apply only AC-line voltage from the same phase or only UL-Class
2 voltage (SELV for CE conformance) to the switching outputs of
both auxiliary switches A and B. Mixed operation is not
permissible.
NOTE: With plenum cables, only UL-Class 2 voltage
(SELV for CE) is permitted.