Addr
Function
Description
Initial
101 DI1 function See Digital inputs R/W 0
102 DI2 function See Digital inputs R/W 1
103 DI3 function See Digital inputs R/W 6
104 DI4 function See Digital inputs R/W 7
105 DO1 function See Digital outputs R/W 11
106 Förlängd ventilation”
1
Seconds R/W 1800 ( 30 min)
107 Temperature sensor type
Bör kalibreras i
överordnat system
0 = LG-NI1000
1 = Ni1000
2 = PT1000
R/W
LG-Ni1000 default
108 Reserved R Always 0
109 Reserved R Always 0
110 Modbus Baudrate 9600, 19200, 38400, 56700 R
111 Modbus Parity 0 = none
1 = even
R
112 Modbus Stop bits 0 or 1 = 1 stop bits
2 = 2 stop bits
R
113 Reserved R Always 0
114 Reserved R Always 0
115 Reserved R Always 0
116 Reserved R Always 0
117 Reserved R Always 0
118 Reserved R Always 0
119 Reserved R Always 0
120 Firmware version Current firmware release R
Locked registers
1001 Register lock functions
Function will be described
if needed
Unique ID in each box will be used to
unlocking functions. This means it will be
individual for each device.
1002
1003 Left damper close timeout In seconds R/W 30
1004 Left damper open timeout In seconds R/W 180
1005 Right damper close
timeout
In seconds R/W 30
1006 Right damper open
timeout
In seconds R/W 180
1007 Close fan on com error 0 = off
1…9 = reserved
10 = after 0 second
110 = after 100 second
R/W 40 (30 seconds)
1008 Close dampers on com
error
0 = off
1…9 = reserved
10 = after 0 second
110 = after 100 second
R/W 40 (30 seconds)
1009 Close damper on fire
alarm
0 = off
1 = on com error
2...9 = reserved
10 = after 0 second
110 = after 100 seconds
R/W 10 (0 seconds)
1010 Left damper motor 0 = Automatic control
1 = Force damper motor OFF
2 = Force damper motor ON
R/W 0
1011 Right damper motor 0 = Automatic control
1 = Force damper motor OFF
2 = Force damper motor ON
R/W 0
1
Delayed closing time of dampers.
…………….. ……………....….