Operating Instructions
10/16
Siemens Modbus för SOC7-128, slave mode SE1Z5996en7
Building Technologies 3 Connection and Configuration 2015-08-26
3.4 Connection via ethernet network
To connect to the system unit SOC7-128 via a Ethernet network a gateway must be
used at the SOC7-128. If the master cannot integrate Modbus/TCP a gateway must
also be installed at that side. The picture bellows shows a topology where a gateway
has been installed also at the master side.
For correct configuration of the gateways, please refer to the specific gateway manuals.
A special modbus/TCP – modbus/serial gateway is recommended, do not use a
standard terminal server.
Tip: Modbus/RTU uses a timeout of 3,5 character instead of a stop character to define
end of message. Communicating over a large network eg. Internet it can cause
problems due to the nature of TCP/IP. It can be a good idea to use modbus/ASCII on
the master side (and only on the master side) when using a gateway. This can only be
realized if a modbus gateway is used rather than a standard terminal server. If the
master only can use Modbus/RTU correct message and character timeouts should be
configured.
3.5 Configure
Default communication settings are : slave address 2, 9600 baud, 8 databits, 1 stopbit,
parity none. Follow the instructions below to configure RS485 and Modbus.
1. Commissioning unit with all settings according to the manual G5996sv4_SOC7-
128sv.pdf before starting to configure Modbus.
2.
Log in with password (2000).
Navigate to menu “Settings – Modbus”.
3. Set the slave address for the device. (1-247, Must be unique).
4. Set Baudrate for RS485 (300-19200)
5. Set Parity for RS485 (None, Even, Odd)
6. Set number of Stopbit for RS485 (1 or 2)
7. Push “ESC” to return to main menu.